Appendix b. status table and settings – Campbell Scientific CR200/CR200X-series Dataloggers User Manual
Page 187

Appendix B. Status Table and Settings
The CR200(X) status table contains system operating status information
accessible via PC software DevConfig, LoggerNet, PC400, RTDAQ, or
PC200W.
TABLE. Common Uses of the Status Table
(Appendix p. 15) lists
some of the more common uses of status table information.
TABLE. Status
Table Fields and Descriptions
(Appendix p. 16) is a comprehensive list of status
table variables with brief descriptions.
Status Table information is easily viewed by going to LoggerNet / PC400 /
RTDAQ / PC200W | Datalogger | Station Status. However, be aware that
information presented in Station Status is not automatically updated. Click the
refresh button each time an update is desired. Alternatively, use the Numeric
displays of the connect screen to show critical values and have these update
automatically, or use Devconfig, which polls the status table at regular intervals
without use of a refresh button. Note that a lot of comms and other activity is
needed to generate the Status Table, so if the CR200(X) is very tight on time,
just getting the Status Table itself repeatedly could push timing over the edge
and cause skipped scans.
Through the continued development of the operating system, the status table has
become quite large. A separate settings table has been introduced to slow the
growth of the status table. To maintain backward compatibility, settings first
included in the status table have been retained, but are also included in the
settings editor.
Feature or
Suspect Constituent
Status Field(s)
to Consult
Reset Data Tables
ResetTables (Enter 8888)
Operating System
OSVersion
OSDate
OSSignature
WatchdogCnt
CRBASIC Program
ProgName
ProgSig
VarOutOfBounds
SkipScan
EEPROM Error
TrapCode
Power Supply
Battery
WatchdogCnt
PakBus
PakBusAddress
Radio
RFInstalled
RfNeAddress
RfHopSeq
RfPwrMode
Rf_ForceOn
Rf_Protocol
RfSignalLevel
15