Horner APG RX371 OCS HERX371C101 User Manual
Page 51
MAN0924-01-EN
CH.10
February 8, 2010 Page 51 of 124 # 1018
The View Protocols Sub-Menu displays two System Settings, none of which are editable.
As mentioned earlier, MJ1 (Port 1) and MJ2 (Port 2) serial ports support downloadable protocols. To
assign a downloadable protocol to a RX-371 serial port, select the Protocol Config item in Cscape’s
Program menu and then setup a protocol for Port 1 or Port 2 (or both of them).
In the View Protocols Sub-Menu, the currently downloaded protocol, if any, and its version number are
displayed for the respective port.
Port 1:
Protocol name
= (None Loaded) or name of the protocol assigned to MJ1
Protocol version
= Blank or version of the protocol assigned to MJ1
Port 2:
Protocol name
= (None Loaded) or name of the protocol assigned to MJ2
Protocol version
= Blank or version of the protocol assigned to MJ2
Set Fkeys
The Set Fkeys Sub-Menu displays two System Settings, both of which are editable.
Fkeys: Momentary
(default) = %K1-5 bits go On/Off as F1-F5 are pressed / released
Toggle = %K1-5 bits toggle each time F1-F5 are pressed
SYS_Fn enable: Yes
(default) = Reset and all clear, system functions enabled
No = Reset and all clear, system functions disabled