beautypg.com

Red Lion GEMINI 52 User Manual

Page 38

background image

Notes:

1. SENSOR VOLTAGE AND CURRENT

The +12 V sensor supply voltage on the “DC OUT” terminal is nominal with

+/-25% variation due to line and internal load variations. All RLC sensors

will accommodate this variation.

2. HI/LO FRQ SELECTION

The HI/LO FRQ selection switch must be set on “LO FRQ” when switch

contacts are used to generate rate input signals. Since the “LO FRQ” mode

also provides very high immunity against electrical noise pickup, it is

recommended that this mode also be used, whenever possible, with electronic

sensor outputs. The “LO FRQ” mode can be used with any type of sensor

output, provided pulse widths never decrease below 5 msec, and the rate does

not exceed 100 cps.

3. V

IL

and V

IH

levels given are nominal values +/-10% when the voltage on “DC

OUT” terminal is +12 VDC. These nominal values will vary in proportion to

the variations in the “DC OUT” terminal voltage, which are caused by line

voltage and load changes.

4. When shielded cable is used, the shield should be connected to “COMM.” at

the counter and left unconnected at the sensor end.

5. Inputs A and B can accept source pulses from other circuits up to +28 V in

amplitude. For voltages above +28 V, a limiting resistor and zener diode

should be used to limit the voltage at the input.

INSTALLATION & REMOVAL OF THE RELAY BOARD

To install the relay board, locate the relay opening at the lower right-hand

corner, on the back of the Gemini 5200. Pull the tab down while sliding the board

into the two slots in the housing. The relay board will seat into the unit, allowing

the tab to return to its original position. To remove the relay board, pull down on

the tab just enough to allow the relay board to slide out. Grasp the six terminal

connector and pull to remove the board.

-36-