beautypg.com

Red Lion GEMINI 52 User Manual

Page 19

background image

Note: When Preset tracking is enabled, before changing Preset 2 via serial

communications, the Preset 2 value must be interrogated in order to establish

the Preset 1 value.

[51 1] Output 1 assigned to Rate A, Output 2 assigned to Rate B

[51 2] Outputs 1 & 2 assigned to Rate B

[51 3] Outputs 1 & 2 assigned to Rate A

[51 4] Output 1 assigned to Rate B, Output 2 assigned to Display C

[51 5] Output 1 assigned to Rate A, Output 2 assigned to Display C

[51 6] Output 1 & 2 assigned to Display C
[51 -1]

[51 -2]

[51 -3]

These modes are the same as above with the

[51 -4]

exception that Preset Tracking is enabled.

[51 -5]

[51 -6]

CODE 52 - OUTPUT 1 TERMINATION MODES

The Gemini 5200 has four “Output 1 termination Modes” which control the

way Output 1 will terminate or reset. In all modes, Output 1 will terminate

immediately when the channel to which it is assigned is manually reset.

A reverse phase mode is available on the Gemini 5200. This refers to the

complementing of the logic state of Output 1. With normal phase operation,

when the display value reaches Preset 1, Output 1 will turn on. The reset

condition of Output 1 is output off. In reverse phase operation, Output 1 turns off

when Preset 1 is reached. The reset condition of Output 1 is output on. (Note: The

state of the relay, if used, is also reversed.) A “-” sign in front of the mode

identifier will provide for reverse phase operation. The absence of a “-” sign will

indicate normal phase operation.
[52 3] TERMINATE AT MANUAL RESET - Output 1 activates when the rate

or display value is greater than or equal to the Preset 1 value. In this mode, once

Output 1 is activated, it does not deactivate until the moment a reset occurs.

Output 1 is set for normal phase operation.

[52 4] TERMINATE AT MANUAL RESET END - This mode is like the

preceding, except Output 1 deactivates when reset ends. Output 1 is set for

normal phase operation.

[52 5] TERMINATE AFTER TIMED OUTPUT 1 - If both outputs are assigned

to the same channel [51 2,3,6], Output 1 will activate when the rate or display

value is below or equal to the Preset 1 value. If each output is assigned to a

different channel [51 1,4,5], Output 1 will activate when the rate or display

value is greater than or equal to the Preset 1 Value.

Output 1 will terminate after the “Timed Output 1 Value” if the Timed Output

Value is less than the update time of the rate or display channel. If the Timed

Output 1 Value is greater than the programmed update time, Output 1 will

appear to be latched on, deactivating when the rate or display value drops

below the Preset [51 1,4,5], or above the Preset [51 2,3,6] and the output time

expires. Output 1 is set for normal phase operation.

[52 6] BOUNDARY MODE - When in boundary mode, the Preset 1 Value

serves as the boundary point. When the rate or display value is less than Preset

1, Output 1 is not activated (normal phase). When the rate or display value is

greater than or equal to Preset 1, Output 1 is activated. If the display value were

to drop below Preset 1, Output 1 would then deactivate. Output 1 is set for

normal phase operation.

[52 -3]

[52 -4]

These modes are the same as above with the exception

[52 -5]

that Output 1 is set for reverse phase operation.

[52 -6]

CODE 53 - TIMED OUTPUT 1 VALUE

The Gemini 5200 has the capability of varying Timed Output 1 from 0.01

second to 599.99 seconds. When the code is entered, instead of a single mode

identifier digit being displayed, six digits will be shown. Refer to “Programming

Presets, Scale Factors, and Timed Output Values” section for more details about

entering. The timed output will be terminated if the unit is manually reset.

The Timed Output 1 Value is used only when in timed output termination

mode, [52 5].
Note: A Timed Output Value of zero cannot be programmed into the Gemini 5200.

If a value of 0 is entered into the display and the “E” key is pressed, the unit will

not enter the 0, but will stay in the data entry mode. If a new value is not entered,

it will time out and the unit will continue to use its previous setting.

-17-