beautypg.com

Red Lion GEMINI 52 User Manual

Page 28

background image

RECEIVING DATA FROM THE GEMINI 5200

Data is transmitted from the Gemini 5200 when a “Transmit Value” or

“Transmit per Print Options” command is sent to the unit, or when the “PRINT

REQ.” terminal is activated. The Gemini 5200 can transmit 7 values: display

channel A, B and C, Presets 1 and 2, and Scale Factors A and B. A list of the

abbreviations used when the Gemini 5200 transmits the values are shown below.

CTA - Rate Display A Value

CTB - Rate Display B Value

CTC - Display C Value

PS1 - Preset 1

PS2 - Preset 2

SFA - Scale Factor A

SFB - Scale Factor B
A typical transmission, with the “PR. ID” (Print ID) switch in the up position,

is shown below.

The first two digits transmitted are the unit address followed by two blank

spaces. If the unit address is 0, the first locations will be left blank. The next three

letters are the abbreviation for the mnemonic value followed by one blank space.

The actual values are transmitted last. Negative values are indicated by a “-”

sign. For positive values, the “+” sign is not transmitted. Overflowed display

values are shown by an asterisk preceding the most significant digit of the value.

The decimal point position will “float” within the data field depending on the

actual value it represents.

For peripheral control purposes, a single line transmission will have a

attached to the end of the above string. For a “T” command or each line of a block

transmission, only the above character string is sent. For the last line of a block

transmission,aisattachedtotheendoftheabovecharacterstring.

An example of a typical serial transmission:

3 CTB 1234.56 < CR> < LF>

If the “Print Request” terminal initiates the transmission, a 400 msec delay is

inserted before the transmission to keep multiple transmissions from

overrunning the printer.

When the Print ID switch is in the down position, the unit will not transmit the

characters before the data value (address, Value ID, spaces) or the 400 msec

printer delay. The same above value when transmitted with the “PR.ID” switch

in the down position, is transmitted as:

1234.56 < CR> < LF>

Note: When using the Gemini with a printer, with the “Print ID” switch in the down

position,someprintersmaynotwork,sincetheprinterdelayisnottransmitted.

PRINT OPTIONS

The various Print Options are used mainly in conjunction with a printer and the

Print Request Terminal. They provide a choice of Gemini 5200 data values to be

printed when either the Print Request Terminal is activated or the “Transmit per

Print Options” (P) command is sent to the Gemini 5200. The various Print

Options available are:

A. Print Rate Display A

B. Print Rate Display B

C. Print Display C

D. Print Display A, B, & C

E. Print Display C, Presets 1 & 2, and Scale Factors A & B

F. Print Display B, Presets 1 & 2, and Scale Factors A & B

G. Print Display A, Presets 1 & 2, and Scale Factors A & B

H. Print Display A, B, & C, Presets 1 & 2, and Scale Factors A & B

A typical print-out is shown below. The Print Options are selected by setting

S3, S4 and S5 on the Serial DIP Switch. See “Current Loop Installation” section

for the various switch settings.

1

CTA

000054

1

PS1

000100

1

PS2

000200

1

SFA

01.0000

1

SFB

02.5000

-26-