beautypg.com

Red Lion GEMINI 52 User Manual

Page 29

background image

CURRENT LOOP INSTALLATION
WIRING CONNECTIONS

When wiring the 20 mA current loop, remove the 7-position terminal block

(TBD), located on the right side of the top board. Refer to the numbers listed with

the terminal descriptions below or on the top label, and install each wire in its

proper location on the terminal block. When all connections are made, replace

the terminal block into its proper location.

It is recommended that shielded (screened) cable be used for serial

communications. This unit meets the EMC specifications using Alpha #2404

cable or equivalent. There are higher grades of shielded cable, such as, four

conductor twisted pair, that offer an even higher degree of noise immunity.

TERMINAL DESCRIPTIONS FOR TERMINAL BLOCK TBD

1. -20 mA SRC (COMM.) - Common for 20 mA SRC and Print Request

terminal.

2. PRINT REQUEST - The Print Request Terminal is pulled low to request the

Gemini 5200 to transmit according to the Print Options mode that has been

selected. (Minimum Activation time = 25 msec.)

3. +20 mA SRC - The 20 mA SRC terminal provides the source current for one of

the loops.

4. SO- (Serial Out-)

5. SO+ (Serial Out+)

The Gemini 5200 transmits the requested data on these terminals. They are

connected in series to the receive input of the device to be connected.

6. SI- (Serial In-)

7. SI+ (Serial In+)

The Gemini 5200 receives commands on these terminals. They are connected

in series with the transmit or output terminals of the device to be connected.

Note: The serial input terminals must be held in the mark condition (current on)

in order for the Gemini 5200 to respond to a Print Request terminal activation.

SERIAL DIP SWITCH SET-UP

The Serial DIP switches are accessible through the side of the Gemini 5200. A

list of the DIP switch positions and their functions are shown in Figure 4.

BR0 & BR1, BAUD RATE - Set-up is shown in Figure 4. When changing the

Baud Rate, the unit should be powered-down and then powered back up again.

The unit will only recognize a baud rate change upon power-up, after

activating the “Print Request” terminal or after a few characters have been

sent at the new baud rate (If the two previous conditions have not occurred, the

Gemini will see the characters as erroneous and it will check the baud rate and

set itself to operate at the new rate).

PR.ID - PRINT ID. - When this switch is in the up position, the Gemini 5200

will print the unit address, data value ID and the data value when a

transmission is requested. The unit will also insert a 400 msec delay between

transmissions when the “P” command or Print Request terminal is used. This

switch position is generally used when the unit is connected with a printer.

When the switch is in the down position, the Gemini 5200 will transmit only the

data value, without the unit address and data ID. The 400 msec delay, described

above, will not be inserted. This switch position usage is intended for applications

where the Gemini is communicating with a computer. In these circumstances

printing the address and value ID and inserting a 400 msec print delay is usually

unnecessary and needlessly slows down communication throughput.

PC0, PC1, & PC2, PRINT OPTIONS - Used to control which values are

printed out when the Print Request terminal is activated or when the Transmit

per Print Options command “P” is sent to the Gemini 5200.

AD0, AD1, AD2, & AD3 UNIT ADDRESS - These switches are used to give

each unit a separate address when more than one unit is connected in the Loop.

See Figure 4, for Switch Set-up.

-27-

FIG. 4: DIP SWITCH SET-UP