beautypg.com

Red Lion G09 9" LCD color touch panel User Manual

Graphite™ series, Dimensions in inches (mm), Safety summary

background image

1

2.06 (52.4)

10.06 (255.6)

6.47

(164.4)

6.7

(171)

(MOUNTING CLIPS INSTALLED)

10.3 (262)

2.97 (76)

Module sold

separately

GRAPHITE™ SERIES

9" Color Touchscreen Operator Interface

Installation Guide

DIMENSIONS In inches (mm)

See the Red Lion website at www.redlion.net or the enclosed

USB thumbdrive for full user manual, Crimson software and

software manual.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in this

literature or on equipment must be observed to ensure personal safety and to

prevent damage to either the instrument or equipment connected to it. If

equipment is used in a manner not specified by the manufacturer, the protection

provided by the equipment may be impaired. Do not use this unit to directly

command motors, valves, or other actuators not equipped with safeguards. To

do so can be potentially harmful to persons or equipment in the event of a fault

to the unit.

ORDERING INFORMATION

DESCRIPTION

PART NUMBER

9" color touch screen, indoor use, 24 VDC powered

G09C0000

9" color touch screen, indoor use, 24 VDC powered,

additional ethernet port

G09C1000

SPECIFICATIONS

POWER: +24 VDC ±20%

Typical Power HMI only:

13 W

Maximum Power HMI only: 20 W

HMI With Module(s):

45 W

Must use a Class 2 circuit according to National Electrical Code (NEC),

NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited

Power Supply (LPS) according to IEC 60950-1 or Limited-energy circuit

according to IEC 61010-1.

Power connection via removable three position terminal block.

ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: -20 to 60 °C

Storage Temperature Range: -20 to 70 °C

Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g

Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)

Operating and Storage Humidity: 0 to 85% max. RH non-condensing

Altitude: Up to 2000 meters

CERTIFICATIONS AND COMPLIANCES:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

IEC/EN 61010-1

RoHS Compliant

UL Listed: File #E302106

Type 4X Indoor / IP66 Enclosure rating (Face only) for all models

CONNECTIONS: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)

Wire Gauge Capacity: One 14 AWG (2.55 mm) solid,

two 18 AWG (1.02 mm) or four 20 AWG (0.61 mm)

CONSTRUCTION: Cast aluminum enclosure with NEMA 4X/IP66 rating for

indoor use only when correctly fitted with the gasket provided. Installation

Category II, Pollution Degree 2.

WEIGHT: 3.39 lb. (1.54 Kg)

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

CAUTION:

Risk of electric shock.

Drawing No. LP0908B
Released 04/14

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

C

US LISTED

UL

R

IND. CONT. EQ.

34AD