3.2 Wiring

3.2.1 RS-485

interface

ƒ Use twisted pair cables with shield.

Recommended cable: UL2464, UL2448, etc.

ƒ The total extension length of the cable is up to 1000 m (3281 ft.). A master station and up to 31 units

can be connected per line.

ƒ Terminate both ends of the cable with 120Ÿ (1/2 W or higher) terminating resistors.

Note: See the specifications of the master for the terminating resistors of the master station unit.

ƒ The shield wire of the cable should be grounded at one place on the master station unit side.
ƒ If this instrument is to be installed where the level of noise applied to this instrument may exceed 1000 V, it is

recommended to install a noise filter in the master station side as below.

Transmission

cable

RS-232C

œRS-485

Noise filter

.

UXF3

Master station

(PC, etc.)

Slave station (UXF3)

TRX1

TRX2

Twisted pair cable with shield

FG

RS-485 interface

or

RS-485 side of the

RS-232C RS-485 converter

Master station side

Slave station (UXF3)

Slave station (UXF3)

TRX1

TRX2

TRX1

TRX2