Bulletin f-107-uxf3-s – Dwyer UXF3 User Manual
Page 30
- 26 -
Relative
address
Register
No.
Data
type
Parameter
Read-out data/Write-in data setting range
Remarks
0042
40067 int
Total mode
0: Start, 1: Stop, 2: Total reset
0044 40069
double Total
constant
*1
64-bit floating data, 0 to 99999999
Unit: Total
004C 40077
double Total
preset
*1
64-bit floating data, 0 to 99999999
Unit: Total
0054 40085
int
Pulse
width
*1
0:5.0msec, 1:10.0msec, 2:50.0msec,
3:100.0msec, 4:200.0msec
0056
40087 int
Burnout
0: Hold, 1: Not use
0058
40089 int
Burnout timer
Decimal point fixed, 0 to 900sec
005A 40091
int
DO1
out
0: Not use, 1: + Total pulse, 2:
Total pulse,
3: Full scale 2, 4: Alarm, 5: Flow switch,
6: Total switch,7: Ao range over,8: Pulse range
over,9: – Flow direction
005C
40093 int
Alarm
0: All, 1: Equipment error, 2: Process error
005E
40095 int
Flow rate switch
0: Upper flow rate, 1: Lower flow rate
0060
40097 double
Upper flow rate
Metric system: 64-bit floating data; 0 to 32m/s
as converted to flow rate
English system: 64-bit floating data
Unit: Flow rate
0068
40105 double
Lower flow rate
Metric system: 64-bit floating data; 0 to 32m/s
as converted to flow rate
English system: 64-bit floating data
Unit: Flow rate
0070 40113
double Total
switch
*1
64-bit floating data, 0 to 99999999
Unit: Total
0078
40121 int
DO1 contact action
0: Active ON, 1: Active OFF
007A 40123
int
DO2
out
0: Not use, 1: + Total pulse, 2:
Total pulse,
3: Full scale 2, 4: Alarm, 5: Flow switch,
6: Total switch,7: Ao range over,8: Pulse range
over,9: – Flow direction
007C
40125 int
Alarm
0: All, 1: Equipment error, 2: Process error
007E
40127 int
Flow rate switch
0: Upper flow rate, 1: Lower flow rate
0080
40129 double
Upper flow rate
Metric system: 64-bit floating data; 0 to 32m/s
as converted to flow rate
English system: 64-bit floating data
Unit: Flow rate
0088
40137 double
Lower flow rate
Metric system: 64-bit floating data; 0 to 32m/s
as converted to flow rate
English system: 64-bit floating data
Unit: Flow rate
0090 40145
double Total
switch
*1
64-bit floating data, 0 to 99999999
Unit: Total
0098
40153 int
DO2 contact action
0: Active ON, 1: Active OFF
009A 40155
int
DO3
out
0: Not use, 1: + Total pulse, 2:
Total pulse,
3: Full scale 2, 4: Alarm, 5: Flow rate switch,
6: Total switch,7: Ao range over,8: Pulse range
over,9: Minus flow direction
009C
40157 int
Alarm
0: All, 1: Equipment error, 2: Process error
009E
40159 int
Flow rate switch
0: Upper flow rate, 1: Lower flow rate
00A0
40161 double
Upper flow rate
Metric system: 64-bit floating data; 0 to 32m/s
as converted to flow rate
English system: 64-bit floating data
Unit: Flow rate
00A8
40169 double
Lower flow rate
Metric system: 64-bit floating data; 0 to 32m/s
as converted to flow rate
English system: 64-bit floating data
Unit: Flow rate
00B0 40177
double Total
switch
*1
64-bit floating data, 0 to 99999999
Unit: Total
00B8
40185 int
DO3 contact action
0: Active ON, 1: Active OFF
00BA
40187 int
DI1 input
0: Not use, 1: Total reset, 2: Zero adjustment
00BC
40189 int
DI1 contact action
0: Active ON, 1: Active OFF
00BE 40191
int
Not
use
00C0 40193
int
1st
row
0: Velocity, 1: Flow rate, 2: Flow rate (%),
3: + Total (actual), 4: + Total pulse, 5:
Total
(actual), 6:
Total pulse
00C2
40195 int
Decimal point position of 1st row
0: *.******, 1: **.*****, 2: ***.****,
3: ****.***, 4: *****.**, 5: ******.*,
6: ********.
Write-in is not
permitted in case
the row is
“Velocity”, “+
Total pulse” or “
Total pulse”.
00C4 40197
Int
2nd
row
0: Velocity, 1: Flow rate, 2: Flow rate (%),
3: + Total (actual), 4: + Total pulse, 5:
Total
(actual), 6:
Total pulse
Bulletin F-107-UXF3-S