Function code, 4 function code – Dwyer UXF3 User Manual
Page 15
- 11 -
5.4 Function
Code
According to MODBUS protocol, register numbers are assigned by function codes.
Each function code acts on specific register number.
This correspondence is shown in Table 5-2, and the message length by function is shown in Table 5-3.
Table 5-2 Correspondence between function codes and objective address
Function code
Resister No.
No. Function
Object
No.
Contents
03
H
Read-out
(continuously)
Holding register
4xxxx
Read-out/write-in word
data
04
H
Read-out
(continuously)
Input register
3xxxx
Read-out word
data
06
H
Write-in
Holding
register
4xxxx
Read-out/write-in word
data
10
H
Write-in
(continuously)
Holding register
4xxxx
Read-out/write-in
word data
Table 5-3 Function code and message length
[Unit:byte]
Command message
Response message
Function
code
Contents
Number of
designatable
data
Minimum Maximum Minimum Maximum
03
H
Read-out of word data
64 words
8
8
7
133
04
H
Read-out of word data
(read-out only)
64 words
8
8
7
133
06
H
Write-in of word data
1 word
8
8
7
7
10
H
Write-in of continuous word data
64 words
11
137
8
8