Function code, 4 function code – Dwyer UXF3 User Manual

Page 15

background image

- 11 -

5.4 Function

Code

According to MODBUS protocol, register numbers are assigned by function codes.

Each function code acts on specific register number.

This correspondence is shown in Table 5-2, and the message length by function is shown in Table 5-3.

Table 5-2 Correspondence between function codes and objective address

Function code

Resister No.

No. Function

Object

No.

Contents

03

H

Read-out
(continuously)

Holding register

4xxxx

Read-out/write-in word

data

04

H

Read-out
(continuously)

Input register

3xxxx

Read-out word

data

06

H

Write-in

Holding

register

4xxxx

Read-out/write-in word

data

10

H

Write-in
(continuously)

Holding register

4xxxx

Read-out/write-in

word data

Table 5-3 Function code and message length

[Unit:byte]

Command message

Response message

Function

code

Contents

Number of

designatable

data

Minimum Maximum Minimum Maximum

03

H

Read-out of word data

64 words

8

8

7

133

04

H

Read-out of word data
(read-out only)

64 words

8

8

7

133

06

H

Write-in of word data

1 word

8

8

7

7

10

H

Write-in of continuous word data

64 words

11

137

8

8