- 7 -

4.

SETTING OF COMMUNICATION CONDITION

In order that the master station and instrument (this instrument) can correctly communicate, following settings are

required.

ƒ All communication condition settings of the master station are the same as those of instruments (this

instrument).

ƒ All instruments (this instrument) connected on a line are set to “Station No.” which are different from each

other. Any “Station No.” is not shared by more than one instrument (when using the RS-485 interface).

4.1 Set

Items

The parameters to be set are shown in the following table. Set them by operating the front panel keys.

Item

Value at
delivery

Setting range

Remarks

Station No.

1

1 to 31
(0:communication function stop)

Set a different value to each station.

Transmission speed

9600 bps

9600 bps, 19200 bps

Parity setting

Odd

None: None parity
Odd: Odd parity
Even: Even parity

Data length

8 bits

Fixed (can not be changed)

Stop bit

1 bit

1 bit, 2 bits

Set the same communi-cation condition
to the master station and all slave
stations.

4.2

Setting operation method

(1) Make communication settings on the maintenance mode screen of the display setting area of the main unit.

Refer to the separate instruction manual for “Fixed Type Ultrasonic Flowmeter,” as required for proper

operation.

Bulletin F-107-UXF3-S