3) message transmission (example), Bulletin f-107-uxf3-s – Dwyer UXF3 User Manual

Page 26

background image

- 22 -

(3) Message transmission (example)

Writing Flow unit = m

3

/h, Range type = single range, Full scale 1 = 300.0 m

3

/h in No. 1 station is shown below.

Flow unit = 0006

H

(= 6

D

)

Range type = 0000

H

(= 0

D

)

Full scale 1 = 4072 C000 0000 0000 (= 300.0

D

) (64-bit double precision float type)

Relative address of Flow unit: 0004

H

(Register No. 40005), Data number: 06

H

Command message composition (byte)

Response message composition (byte)

Station No.

01

H

Station

No.

01

H

Function code

10

H

Function

code

10

H

Upper 00

H

Upper

00

H

Write-in start No.
(relative address) Lower 04

H

Write-in start No.
(relative address) Lower 04

H

Upper 00

H

Upper

00

H

Write-in word
number

Lower 06

H

Write-in word
number

Lower 06

H

Write-in byte number

0C

H

Lower

01

H

Upper 00

H

CRC data

Upper CA

H

First write-in
word data

Lower 06

H

Upper 00

H

Next write-in
word data

Lower 00

H

Upper 40

H

Next write-in
word data

Lower 72

H

Upper C0

H

Next write-in
word data

Lower 00

H

Upper 00

H

Next write-in
word data

Lower 00

H

Upper 00

H

Last write-in
word data

Lower 00

H

Lower 51

H

CRC data

Upper AB

H

Point

For handling of floating data, refer to Section 7.1.

For transmission format of each data, refer to the address map (Chapter 7.)

Caution

If the write-in command message is sent to any slave station during the

FIX process, response is not returned from it.

Bulletin F-107-UXF3-S