Write-in of Word Data [Function code:06
H
]
Function code
Max. word number
write-in in one
message
Relative data
address
Register No.
Kind of data
0140
H
㧙014F
H
40321
㧙40336
Storage enable data
06
H
1
word
0150
H
㧙0171
H
40337
㧙40370
Storage disable data
(1) Message composition
Command message composition (byte)
Response message composition (byte)
Station No.
Station No.
Function code
Function code
Upper
Upper
Write-in
designate No.
(relative address) Lower
Write-in
designate No.
(relative address)
Lower
Upper Upper
Write-in word
data
Lower
Write-in word data
Lower
Lower
Lower
CRC data
Upper
CRC data
Upper
(2) Function explanation
Designated word data is written in write-in designate No. Write-in data are transmitted from master station in
the order of upper and lower bytes.
The current value is returned when the write-in data does not fall within the effective range.
(3) Message transmission (example)
The following shows an example of transmitting the “Zero adjustment” key command to No.1 station.
Key operation command Relative address: 0140
H
Command message composition (byte)
Response message composition (byte)
Station No.
01
H
Station
No.
01
H
Function code
06
H
Function
code
06
H
Upper 01
H
Upper
01
H
Write-in
designate No.
(relative address) Lower 40
H
Write-in
designate No.
(relative address)
Lower 40
H
Upper 00
H
Upper
00
H
Write-in word
data
Lower 01
H
“Brightness
UP” key
command
Write-in word data
Lower
01
H
Lower 48
H
Lower 48
H
CRC data
Upper 22
H
CRC data
Upper 22
H
Bulletin F-107-UXF3-S