[Setting]....................... Sends the setting of the selected item (check box set to ON (

;)), reflecting the response

value on the setting.

[READ] ....................... Reads the setting of the selected item (check box set to ON (

;)), reflecting the response

value on the setting.

[Save] .......................... Reflects the setting sent by pressing the [Setting] button on the flow transmitter. Be sure to

press the [Save] button if the setting is changed.

[Check ON/OFF]......... Set the check box to ON to select all the items (to set all the check boxes to ON (

;)). Set

the check box to OFF (

†) to release the selection of all the items (to set all the check boxes

to OFF (

†)).

Table 9-17 < Detailed Setting >

Item Content

TRANSMIT PATTERN

Select from BURST 1, BURST 2, BURST 3, BURST 4, BURST 5, CHIRP 4, CHIRP 8,
and RESERVE.

TRANSMIT count

In case operation mode is normal:

Select from 8, 16, 32, 64, 128 and 256.

In case operation mode is High Speed:

Select from 4, 8, 16, 32, 64 and 128.

MEASURE METHOD

Select from METHOD 1, METHOD 2 and METHOD 3.

SATURATION

Enter in the range of numeric 0 to 512.

SIGNAL BALANCE

Enter in the range of numeric 0 to 100%.

SIGNAL PEEK

Select from 0.125 V (1024), 0.25 V (2048), 0.375 V (3072), and 0.5 V (4096).

TRIGGER LEVEL

With selection of AUTO/MANUAL, in case of MANUAL, input range of numeric 10.00
to 90.00% at right column.

WINDOW CONTROL

With selection of AUTO/MANUAL, in case of MANUAL, input range of numeric 1 to
16383 in each column of U: OPEN TIME/D: OPEN TIME.

AGC GAIN

With selection of AUTO/MANUAL, in case of MANUAL, input range of numeric 1.28 to
98.56% in each column of U: AGC/D: AGC.

TRANS. WAIT TIME

Enter in the range of numeric 1 to 30 msec.