6. Automation Software

The frame formats exchanged with the automation software through the serial port for each of the
emulated receivers are as follows:

6.1. Frame formats

a) Sur-gard Format

MLR2000

5RRLLLs18AAAAQXYZGGCCC[T]

Where:

RR: Receiver number

LLL: Line number

s: Space

18: Contact-Id format identifier

AAAA: Four-digit account code

Q: Qualificator, E= New event or opening; R=Restoration or closing; P=Previous event.

XYZ: Type of event and code for this

GG: Number or group or partition.

CCC: Zone number or user identifier.

[T]: 14 hex character as terminator

Heartbeat

1RR000sssssssssss@ssss[T]

Where:

RR: Receiver number

s: Space

@: Supervision character

[T]: 14 hex character as terminator

MLR2D

5RRLs18AAAAQXYZGGCCC

Where:

RR: Receiver number

L: Line number

s: Space

18: Contact-Id format identifier

AAAA: Four-digit account code

Q: Qualificator, E= New event or opening; R=Restoration or closing; P=Previous event.

XYZ: Type of event and code for this

GG: Number or group or partition.

CCC: Zone number or user identifier.

[T]: 14 hex character as terminator