4.2. Installation requirements
a) General
1. The system provides encrypted line security via packet switched data network. The system may be
installed to protect a single property, or non-contiguous properties under a single ownership.
Employs the CFB code which is certified by NIST, Cert No. 280.
2. For the 200 sec. supervision, the system "polls" the VisorALARM PLUS 2U receiver via packet
switched data network. Note, 90 sec. Supervision is required for commercial fire applications.
3. The number of separate signals on a single channel is limited to 1000.
4. Supervision signals between premises alarm equipment and supervising station alarm receiver
equipment shall be managed by the supervising station receiving equipment and not an
intermediary network agent, device or service.
5. Message authentication is conducted via procedural algorithmic processing.
6. Network addressing of devices must not make use of public Domain Name Servers.
7. Remote panel programming or configuration access shall require the use of a valid password, the
panel’s account or IP address number, and a receiver key code which is established between the
panel and receiver automatically and without user knowledge of the specific code
8. The display message “350” (communication trouble) may Indicate compromise attempt.
9. The VisorALARM PLUS 2U supports the Contact-ID protocol.
10. For central station and proprietary use, the acknowledgement signal must be enabled.
11. The wiring connections between the mIP/IPDACT and the Listed control panel are to be made
within 20 feet (6.1 m) and are to be enclosed in conduit.
12. For a dual signal line transmission system with encrypted line security, alarms are transmitted over
both the IP and telco lines.
13. For Canadian Certifications (central station, proprietary), the signaling line or communication
channel is designated as Level III.
14. For Canadian Certifications, the mIP/IPDACT is intended to be connected to a Listed panel that is
ULC or cUL Listed to C1023, C1076, and S304.
b) BURGLAR ALARM (CENTRAL STATION): DACT, PACKET SWITCHED
DATA NETWORK
1. The maximum total current draw is 1 A.