route 0.0.0.0 0.0.0.0 172.28.1.1 1
;
exit
;
dump-command-errors
end
; --- end ---
Config>

For validity purposes, save the configuration and restart the device.

ARLY-1 Cfg>exit
Config>save
Save configuration (Yes/No) [No]? y

Performing memory requirements calculations, please wait
Building system configuration, please wait
Configuration built, saving ...
OK on Flash
Config>
*restart
Are you sure to restart the system(Yes/No)? y

The pattern configuration can be repeated, if required, in the backup device. However, the
synchronization software itself passes the VisorALARM PLUS 2U pattern configuration to the
backup. Synchronization is not automatic; it depends on the polling-sync-time parameter
which pertains to the backup parameters. The default value is 5 minutes. Consequently, the
configuration changes which have been produced during this period are synchronized every five
minutes, both in the main VisorALARM PLUS 2U and the backup.

c) Installing and registering mIP/IPDACTs

In the mIP/IPDACT, the installer must configure the mIP/IPDACT with the minimum installer
configuration, as indicated in the mIP/IPDACT installation manual. The following parameters must
be configured:

mIP/IPDACT IP address and mask:

192.168.80.100 255.255.255.0

mIP/IPDACT access gateway:

192.168.80.1

mIP/IPDACT account number:

101234

VisorALARM PLUS 2U IP address:

215.99.32.3

UDP port:

20300

Subsequently, the installer must proceed to the register using the password (99887766). If the ARLY
interface events are enabled in the VisorALARM PLUS 2U, check for the arrival of the register
petition and the sending of the configuration to the mIP/IPDACT, as well as the event sending which
notifies the installation of a new mIP/IPDACT.

Config>09/02/03 09:01:28 ARLY.001 UDP Rx frm sz 80
09/02/03 09:01:28 ARLY.010 RSRVC Rx frm
09/02/03 09:01:28 ARLY.002 UDP Tx frm sz 152
09/02/03 09:01:28 ARLY.024 RREGSTR accnt 101234 inst 99887766
09/02/03 09:01:28 ARLY.008 FMS st 2 ev 8
09/02/03 09:01:28 ARLY.005 SL Tx 56 181234E53100000
09/02/03 09:01:29 ARLY.004 SL Rx ACK
09/02/03 09:01:29 ARLY.008 FMS st 4 ev 1
09/02/03 09:01:29 ARLY.020 STOR delete, 500 free

As a result of the register process, the mIP/IPDACT information is stored in the VisorALARM PLUS
2U so it is unnecessary to re-register the mIP/IPDACT if the VisorALARM PLUS 2U is restarted.