VISORALARM - Installation
II - 16
Doc.DM374-I
Ver.1.0
Figure 7. Arrangement of inputs/outputs in ConnectorI/O (VA-UD)
The two outputs are relays with a rated voltage of 30 volts CC and a rated amperage of 2A CC. The
relays are normally open.
q
Output1: This output is dedicated for watchdog indication.
q
Output2: This is a general purpose output. The factory configuration for this output is to close
the relay in cases where some unrestored trouble alarm s(3XX CONTACT-ID code) exist with
account 0, i.e., an trouble alarm signaled by the VisorALARM and not restored.
The two inputs have RS-232 levels (-12V/+12V, -12V input inactive, +12V input active).
q
Input1: This is a general purpose input. The factory configuration for this input is to detect a
failure in the AC main signaled by a UPS device.
q
Input2: This is a general purpose input. The factory configuration for this input is to detect a
low battery signaled by a UPS device.
e) Configuration connection
The IP VisorALARM PLUS 2U receiver routers have a female DB-9 connector in the rear panel
referred to as “AUX” which provides access to the device local console for configuration and
monitoring purposes. In order to use this, you must connect to the “AUX” port to an asynchronous
terminal (or to a PC with terminal emulation).