App index, Tc sets the background color, Tp sets auto group switching – Yokogawa Button Operated MV2000 User Manual
Page 90: Tr sets auto monitor recovery, Tq sets a timer, Tk sets a match timer
4-17
Commands
M-4662
1
2
3
4
5
6
7
App
Index
SQ
Sets the LCD brightness and
screen backlight saver
Syntax
SQ p1,p2,p3,p4
p1
LCD brightness
1–8
RD-MV1000
1–6
RD-MV2000
p2
Type of display backlight saver function
OFF
Disable the saver function
DIMMER
Dim
TIMEOFF
Turn OFF
p3
Time to switch to saver mode
1MIN
, 2MIN, 5MIN, 10MIN, 30MIN, 1H
p4
Event that causes the MV to return from
saver mode
KEY
Pressing of a key
KEY+ALARM
Pressing of a key or an alarm
occurrence
Query
SQ?
Example
Set the LCD brightness to 2 and the screen
backlight saver function to dim. Set the time to
switch to saver mode to 5 minutes and the event
that causes the MV to return from saver mode to
pressing of a key.
SQ2,DIMMER,5MIN,KEY
Description If p2 is set to OFF, do not specify p3 or p4.
TC
Sets the background color
Syntax
TC p1,p2
p1
Display screen (WHITE, BLACK)
p2
Historical trend display (WHITE, CREAM,
LIGHTGRAY, BLACK)
Query
TC?
Example
Set the display background to black and the
historical display background to cream.
TCBLACK,CREAM
TP
Sets auto group switching
Syntax
TP p1
p1
Auto scroll time (5S, 10S, 20S, 30S, 1MIN)
Query
TP?
Example
Switch the group at 5-s intervals.
TP5S
TR
Sets auto monitor recovery
Syntax
TR p1
p1
Auto recovery time (OFF, 1MIN, 2MIN,
5MIN, 10MIN, 20MIN, 30MIN, 1H)
Query
TR?
Example
Set the auto recovery time to 5 minutes.
TR5MIN
TQ
Sets a timer
If p2 is set to OFF (no timer)
Syntax
TQ p1,p2
p1
Timer number (1 to 4)
p2
Timer type (OFF)
If p2 is set to ABSOLUTE (absolute time)
Syntax
TQ p1,p2,p3,p4
p1
Timer number (1 to 4)
p2
Timer type (ABSOLUTE)
p3
Time interval (1MIN to 6MIN, 10MIN, 12MIN,
15MIN, 20MIN, 30MIN, 1H to 4H, 6H, 8H,
12H, 24H)
p4
Reference time (hh)
hh
Hour (00 to 23)
If p2 is set to RELATIVE (relative time)
Syntax
TQ p1,p2,p3,p4
p1
Timer number (1 to 4)
p2
Timer type (RELATIVE)
p3
Time (hh:mm)
hh
Hour (00 to 24)
mm
Minute (00 to 59)
p4
Reset at computation start (ON/OFF)
Query
TQ[ p1]?
Example
Set the timer number 1 timeout value to 10 hours 30
minutes. Do not reset at start.
TQ1,1,RELATIVE,10:30,OFF
TK
Sets a match timer
If p2 is set to OFF (not use a match timer)
Syntax
TK p1,p2
p1
Timer number (1 to 4)
p2
Timer designation (OFF)
If p2 is set to DAY (time designation)
Syntax
TK p1,p2,p3,p4,p5
p1
Timer number (1 to 4)
p2
Timer designation (DAY)
p3
Day (1 to 28)
p4
Time (hh:mm) (00:00 to 23:59)
p5
Timer operation (SINGLE, REPEAT)
SINGLE
Single operation
REPEAT
Repetitive operation
If p2 is set to WEEK (day of week/time designation)
Syntax
TK p1,p2,p3,p4,p5
p1
Timer number (1 to 4)
p2
Timer designation (WEEK)
p3
Designation of the day of the week (SUN,
MON, TUE, WED, THU, FRI, SAT)
p4
Time (hh:mm) (00:00 to 23:59)
p5
Timer operation (SINGLE, REPEAT)
4.4 Setting Commands (Setting)