beautypg.com

App index checking the modbus operating status – Yokogawa Button Operated MV2000 User Manual

Page 49

background image

M-4662

2-35

Using

the
Ethernet

Interface

1

2

3

4

5

6

7

App

Index

Checking the Modbus Operating Status

Displaying the Modbus Operating Status

◊ Press DISP/ENTER and then select INFORMATION > MODBUS CLIENT

Note

To show the MODBUS CLIENT on the display selection menu, you need to change the setting
using the menu customize feature. Carry out the following steps.
◊ Press MENU and then select Menu tab >

M

enu customize > Display menu

1. Select INFORMATION > MODBUS CLIENT using the arrow keys.
2. Press the View soft key.

Server device host names or IP addresses

Register numbers

MV channels

Detail code

Status lamp

Cursor used to select a command

(Used to resume command transmission from the front panel keys)

Communication conditions

• Communication Conditions

The Read cycle and Connect.retry settings are displayed.

• Communication Status

The MV displays the communication status using status lamps and detail codes.

Status Lamp

Detail Code Meaning

Green

Good

Communication is operating normally.

Yellow

Command is readying.

Orange

Trying to establish a TCP connection.

Red

Communication is stopped.

Common to yellow,
orange, and red

None

No response from the server device.

Func

The server device cannot execute the command from the MV.

Regi

The server device does not have the specified register.

Err

There is an error in the response data from the server device.

Link

Ethernet cable is disconnected.

Host

Unable to resolve the IP address from the host name.

Cnct

Failed to connect to the server.

Send

Failed to transmit the command.

BRKN

Failed to receive the response data or detected a
disconnection.

(Space)

The detail code does not appear until the status is
confirmed when communication is started.

2.9 Reading/Writing Data on Another Device from the MV via Modbus

This manual is related to the following products: