Checking the Modbus Operating Status
Displaying the Modbus Operating Status
◊ Press DISP/ENTER and then select INFORMATION > MODBUS CLIENT
Note
To show the MODBUS CLIENT on the display selection menu, you need to change the setting
using the menu customize feature. Carry out the following steps.
◊ Press MENU and then select Menu tab >
M
enu customize > Display menu
1. Select INFORMATION > MODBUS CLIENT using the arrow keys.
2. Press the View soft key.
Server device host names or IP addresses
Register numbers
MV channels
Detail code
Status lamp
Cursor used to select a command
(Used to resume command transmission from the front panel keys)
Communication conditions
• Communication Conditions
The Read cycle and Connect.retry settings are displayed.
• Communication Status
The MV displays the communication status using status lamps and detail codes.
Status Lamp
Detail Code Meaning
Green
Good
Communication is operating normally.
Yellow
Command is readying.
Orange
Trying to establish a TCP connection.
Red
Communication is stopped.
Common to yellow,
orange, and red
None
No response from the server device.
Func
The server device cannot execute the command from the MV.
Regi
The server device does not have the specified register.
Err
There is an error in the response data from the server device.
Link
Ethernet cable is disconnected.
Host
Unable to resolve the IP address from the host name.
Cnct
Failed to connect to the server.
Send
Failed to transmit the command.
BRKN
Failed to receive the response data or detected a
disconnection.
(Space)
The detail code does not appear until the status is
confirmed when communication is started.
2.9 Reading/Writing Data on Another Device from the MV via Modbus