App index, Yv sets e-mail recipient addresses, Yw sets the e-mail sender address – Yokogawa Button Operated MV2000 User Manual
Page 108: Yx sets the e-mail smtp server name, Yj sets a modbus client destination server
4-35
Commands
M-4662
1
2
3
4
5
6
7
App
Index
To send system notifications
Syntax
YU p1,p2,p3,p4,p5,p6,p7
p1
Transmitted content (SYSTEM)
p2
Recipient 1 ON/OFF
p3
Recipient 2 ON/OFF
p4
Include source URL ON/OFF
p5
Subject (up to 32 alphanumeric characters)
p6
Header 1 (up to 64 characters)
p7
Header 2 (up to 64 characters)
Query
YU[ p1]?
Example
Send system notification e-mail messages
including the source URL to recipient 1. Set the
subject to “SystemAlert” and header 1 to “LP2.”
YUSYSTEM,ON,OFF,ON,SystemAlart,LP2
To send report generation notifications
Syntax
YU p1,p2,p3,p4,p5,p6,p7
p1
Transmitted content (REPORT)
p2
Recipient 1 ON/OFF
p3
Recipient 2 ON/OFF
p4
Include source URL ON/OFF
p5
Subject (up to 32 alphanumeric characters)
p6
Header 1 (up to 64 characters)
p7
Header 2 (up to 64 characters)
Query
YU[ p1]?
Example
Send report generation notification e-mail
messages including the source URL to recipient
1. Set the subject to “Report” and header 1 to
“LP2.”
YUREPORT,ON,OFF,ON,Report,LP2
Description • For the contents of system notifications, see
section 2.3.
• Report generation notification can be used on
models with the /M1 math option.
• For e-mail settings, see section 2.3.
YV
Sets e-mail recipient addresses
Syntax
YV p1,p2
p1
Recipient selection
1
Recipient 1
2
Recipient 2
p2
Recipient address (up to 150 alphanumeric
characters)
Query
YV[p1]?
Example
Set recipient 1 to “[email protected]”
and “[email protected].”
YV1,[email protected] mvuser2@
daqstation.com
Description • To set multiple recipients, separate each
recipient with a space.
• For e-mail settings, see section 2.3.
YW
Sets the e-mail sender address
Syntax
YW p1
p1
Sender address (up to 64 alphanumeric
characters)
Query
YW?
Example Set the sender address to “mvadv.”
YWmvadv
Description For e-mail settings, see section 2.3.
YX
Sets the e-mail SMTP server
name
Syntax
YX p1,p2,p3
p1
SMTP server name (up to 64 characters)
p2
Port number (0 to 65535)
p3
Authentication
OFF
No authentication
POPBEFORESMTP
Execute POP Before
SMTP
Query
YX?
Example Set the SMTP server to “smtp.daqstation.com,”
the port number to “25,” and execute POP
Before SMTP.
YX smtp.daqstation.com,25,POPBEFORESMTP
Description For e-mail settings, see section 2.4.
YJ
Sets a Modbus client destination
server
Syntax
YJ p1,p2,p3,p4,p5
p1
Server number (1 to 16)
p2
Port number (0 to 65535)
p3
Host name (up to 64 characters)
p4
Unit number registration
AUTO
Not use the unit number
FIXED
Use a fixed unit number
p5
Unit number (0 to 255)
Query
YJ[ p1]?
Example Set the port number of server number 3 to 502,
the host name to RD-MV2000, the unit number
registration to FIXED, and the unit number to
127.
YJ3,502,RD-MV2000,FIXED,127
4.6 Basic Setting Commands