4 setting commands (setting), Sr sets an input range – Yokogawa Button Operated MV2000 User Manual
Page 83
4-10
4.4
Setting Commands (Setting)
M-4662
4.4 Setting Commands
(Setting)
SR
Sets an input range
To set a channel to skip
Syntax
SR p1,p2
p1
Measurement channel number
p2
Setting type (SKIP)
Query
SR[ p1]?
Example
Skip channel 001.
SR001,SKIP
Description • You cannot execute this command while the
MV is measuring or computing.
• A channel set to SKIP is not measured.
• Set parameter p1 according to the table in
section 4.3.
To set a channel to voltage, TC, RTD, or ON/OFF
input
Syntax
SR p1,p2,p3,p4,p5
p1
Measurement channel number
p2
Input type
VOLT
DC voltage
TC
Thermocouple
RTD
RTD
DI
ON/OFF input
p3
Measurement range
p4
Span lower limit
p5
Span upper limit
Query
SR[ p1]?
Example
Set the channel 001 input type to TC type R, the
span lower limit to 0°C, and the span upper limit
to 1760.0°C.
SR001,TC,R,0,17600
Description • You cannot execute this command while the
MV is measuring, computing, or generating a
report.
• Set parameters p1 and p3 according to the
table in section 4.3.
• For parameters p4 and p5, enter a value using
5 digits or less excluding the decimal point.
To set a channel to difference computation
Syntax
SR p1,p2,p3,p4,p5,p6,p7
p1
Measurement channel number
p2
Setting type (DELTA)
p3
Input type
VOLT
DC voltage
TC
Thermocouple
RTD
RTD
DI
ON/OFF input
p4
Measurement range
p5
Span lower limit
p6
Span upper limit
p7
Reference channel number (measurement
channel number)
Query
SR[ p1]?
Example Set the channel 010 setting type to differential
computation between channels with the reference
channel set to 001, and set the input type to TC.
Set the measurement range to R. Set the span
lower limit to 10.0°C and span upper limit to 100.0°C.
SR010,DELTA,TC,R,100,1000,001
Description • You cannot execute this command while the
MV is measuring, computing, or generating a
report.
• Set parameters p1 and p4 according to the
table in section 4.3.
• For parameters p5 and p6, enter a value
using 5 digits or less excluding the decimal
point.
To set a channel to scaling
Syntax
SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10
p1
Measurement channel number
p2
Setting type (SCALE)
p3
Input type
VOLT
DC voltage
TC
Thermocouple
RTD
RTD
DI
ON/OFF input
p4
Measurement range
p5
Span lower limit
p6
Span upper limit
p7
Scaling lower limit (–30000 to 30000)
p8
Scaling upper limit (–30000 to 30000)
p9
Scaling decimal place (0 to 4)
p10
Unit (up to six alphanumeric characters)
Query
SR[ p1]?
Example Convert the DC voltage measured on channel
002 to DC current. Set the input range to 6 V,
the span lower limit to 1 V, the span upper limit
to 5 V, the scaling lower limit to 1.00 A, and the
scaling upper limit to 5.00 A.
SR002,SCALE,VOLT,6V,1000,5000,100,5
00,2,A
Description • You cannot execute this command while the
MV is measuring, computing, or generating a
report.
• Set parameters p1 and p4 according to the
table in section 4.3.
• For parameters p5 and p6, enter a value
using 5 digits or less excluding the decimal
point.
• Set all parameters p7, p8, and p9 or omit all
three parameters.
To set a channel to square root computation
Syntax
SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11
p1
Measurement channel number
p2
Setting type (SQRT)
p3
Measurement range
p4
Span lower limit
p5
Span upper limit
p6
Scaling lower limit (–30000 to 30000)
p7
Scaling upper limit (–30000 to 30000)