beautypg.com

App index, Xj sets an rjc, Wu sets environment settings – Yokogawa Button Operated MV2000 User Manual

Page 102

background image

4-29

Commands

M-4662

1

2

3

4

5

6

7

App

Index

XJ

Sets an RJC

To use the internal compensation circuit

Syntax

XJ p1,p2
p1

Measurement channel number

p2

Reference junction compensation

designation (INTERNAL)

Query

XJ[ p1]?

Example

Set the channel 001 RJC to the internal
compensation circuit.
XJ001,INTERNAL

To use an external RJC

Syntax

XJ p1,p2,p3
p1

Measurement channel number

p2

Reference junction compensation

designation (EXTERNAL)

p3

External RJC value (–20000 to 20000)

Query

XJ[ p1]?

Example

Set the channel 002 RJC to external and set the
compensation value to 0 μV.
XJ002,EXTERNAL,0

Description • Set parameter p1 according to the table in

section 4.3.

• The unit of parameter p3 is μV.

WU

Sets environment settings

Setup items

GENERAL,BATCH,DISPLAY,MESSAGE,INPU
T, ALARM,SECURITY,MEDIA,MATH,REPORT,
SERVICEPORT,DECIMALPOINT,POP3

General environment settings

Syntax

WU p1,p2,p3
p1

Setting type (GENERAL)

p2

Tag/channel number selection

TAG
CHANNEL

Channel number

p3

Language

ENGLISH
JAPANESE
CHINESE
GERMAN
FRENCH
KOREAN

Example

Select tag display and set the language to
English.
WUGENERAL,TAG,ENGLISH

To set the batch function

Syntax

WU p1,p2,p3,p4
p1

Setting type (BATCH)

p2

Batch function ON/OFF

p3

Number of lot number digits (OFF, 4, 6, 8)

p4

Auto increment ON/OFF

Description Parameters p3 and p4 are valid only when p2 is

ON.

To set the display

Syntax

WU p1,p2
p1

Setting type (DISPLAY)

p2

Trend type (T-Y)

p3

Partial expansion ON/OFF

p4

Trend update rate switching ON/OFF

To set message settings

Syntax

WU p1,p2,p3,p4
p1

Setting type (MESSAGE)

p2

Method of writing messages from keys

COMMON

Applied to all display groups

SEPARATE

Applied to a specified display

group

p3

Power failure message ON/OFF

p4

Change message ON/OFF

To set the input

Syntax

WU p1,p2
p1

Setting type (INPUT)

p2

Detection of values exceeding the scale

FREE

When the measurement range is
exceeded

OVER

When ±105% of the scale is
exceeded

To set alarm settings

Syntax

WU p1,p2
p1

Setting type (ALARM)

p2

Alarm suppression function ON/OFF

To set security settings

Syntax

WU p1,p2,p3
p1

Setting type (SECURITY)

p2

Keys

OFF

Disable security

KEYLOCK

Lock the keys

LOGIN

Enable the login function

p3

Communication

OFF

Disable security

LOGIN

Enable the login function

Set media settings

Syntax

WU p1,p2,p3
p1

Setting type (MEDIA)

p2

Auto save function ON/OFF

p3

Media FIFO ON/OFF

Example

Use media FIFO.
WUMEDIA,ON,ON

Description Parameter p3 is valid only when p2 is ON.