beautypg.com

3 modbus protocol, Modbus client/master, Modbus server/slave – Yokogawa Button Operated MV2000 User Manual

Page 14

background image

1-8

M-4662

1.3

Modbus Protocol

Modbus Client/Master

• The MV can connect to a Modbus server or slave device and read and write to the

device’s internal registers.

The MV can handle the data that is read from the registers as communication input

data on a computation channel (computation function

1

). The MV can also handle the

data on an external input channel.

2

The MV can write measured and computed data to the registers.

1 /M1 option.
2 RD-MV2000 with the /MC1 option.

• For details on the Modbus function codes that the MV supports, see section 7.3.
• For the settings to use the Modbus client feature, see section 2.9. For the settings to

use the Modbus master feature, see sections 3.3, 3.5, and 3.6.

Server Device Connection Example

Modbus server device

MV (client)

Ethernet

MV

Modbus Server/Slave

• A Modbus client (master) device can connect to an MV, a Modbus server (slave)

device, to read the measured, computed,

1

or external input

2

data that is written in the

input register or to read or write data to communication input data

1

or to an external

input channel

2

through the MV hold register.

1 /M1 option.
2 RD-MV2000 with the /MC1 option.

• For details on the Modbus function codes that the MV supports, see section 7.3.
• For the settings to use the Modbus client feature, see section 2.8. For the settings to

use the Modbus master feature, see sections 3.3, 3.4, and 3.6.

Example of a Connection with a Modbus Master Device

Modbus master device

MV (slave)

Serial communication

MV

This manual is related to the following products: