Yokogawa Button Operated MV2000 User Manual
Page 161
7-8
M-4662
Input Register
Data
Data Type
36001
List of alarms of measurement channels 001 to 004
Bit string
|
|
36012
List of alarms of measurement channels 045 to 048
• Register structure
4ch 3ch 2ch 1ch
Level 3
Level 4
Level 2
Level 1
Indicates the alarm statuses of four channels in a register. Set to 1 when
alarm is activated. The figure above is an example of register 36001
(measurement channels 001 to 004).
36021
List of alarms of computation channels 101 to 104
Bit string
|
|
36035
List of alarms of computation channels 157 to 160
• Register structure: Same as the list of alarms of measurement channels.
36041
List of alarms of external input channels 201 to 204
Bit string
|
|
36100
List of alarms of external input channels 437 to 440
• Register structure: Same as the list of alarms of measurement channels.
• Input registers 36001 to 36100 can be accessed consecutively. All unassigned register bits
are read as zeroes.
Input Register
Data
Data Type
39001
Year
16-bit signed integer
39002
Month
39003
Day
39004
Hour
39005
Minute
39006
Second
39007
Millisecond
39008
(Reserved)
7.3 Modbus Protocol Specifications