Yokogawa Button Operated MV2000 User Manual
Page 125
5-7
M-4662
Responses
1
2
3
4
5
6
7
App
Index
tt
Command name (SR, SA···, XA, XI···)
sss···s
Setting/basic setting data (variable length, one line)
• Example
EA
SR001,VOLT,20mV,0,20
SR002,VOLT,20mV,0,20
···················
EN
Decimal Place and Unit Information
• The MV returns decimal place and unit information in response to an FE command.
• You can use the CB command to specify whether or not the MV will return the data of
measurement channels set to SKIP and computation channels set to OFF.
•
Syntax
The MV returns the data for each channel in the following syntax.
EACRLF
s_cccuuuuuu,ppCRLF
··················
ENCRLF
s
Data status (N, D, or S)
N:
Normal
D:
Differential input
S:
Skip (When the measurement range is set to SKIP for a
measurement channel or when the channel is turned OFF for a
computation channel)
ccc
Channel number (3 digits)
001
to 048:
Measurement channel
101
to 160:
Computation channel
201
to 440:
External input channel
uuuuuu
Unit information (six characters, left-justified)
mV____:
mV
V_____:
V
^C____:
°C
xxxxxx:
(User-defined character string)
pp Decimal place (00 to 04)
No decimal (00000) for 00.
One digit to the right of the decimal (0000.0) for 01.
Two digits to the right of the decimal (000.00) for 02.
Three digits to the right of the decimal (00.000) for 03.
Four digits to the right of the decimal (0.0000) for 04.
_
Space
•
Example
EA
N 001mV ,01
N 002mV ,01
EN
5.2 Text Data Output Format