Measured, computed, and external input data – Yokogawa Button Operated MV2000 User Manual

Page 126

background image

5-8

M-4662

Measured, Computed, and External Input Data

• The MV returns measured, computed, and external input data in response to an FD

command.

• You can use the CB command to specify whether or not the MV will return the data of

measurement channels set to SKIP and computation channels set to OFF.

Syntax

The MV returns the data along with the date and time information for each channel in

the following syntax.
EACRLF
DATE_yy/mo/ddCRLF
TIME_hh:mm:ss.mmmtCRLF
s_ccca

1

a

2

a

3

a

4

uuuuuufdddddE-ppCRLF

····························
ENCRLF

yy

Year (00 to 99)

mo

Month (01 to 12)

dd

Day (01 to 31)

hh

Hour (00 to 23)

mm

Minute (00 to 59)

ss

Second (00 to 59)

mmm

Millisecond (000 to 999. A period is placed between seconds and

milliseconds.)

t

Reserved (Space.)

s

Data status (N, D, S, O, E, or B)

N:

Normal

D:

Differential input

S:

Skip

O:

Overflow

E:

Error

B:

Burnout

ccc

Channel number (3 digits)
001

to 048:

Measurement channel

101

to 160:

Computation channel

201

to 440:

External input channel

a

1

a

2

a

3

a

4

a

1

Alarm status (level 1)

a

2

Alarm status (level 2)

a

3

Alarm status (level 3)

a

4

Alarm status (level 4)

(Each status is set to H, L, h, l, R, r, T, t, or space.)
((H: high limit alarm, L: low limit alarm, h: difference high-limit alarm, l:

difference low-limit alarm, R: high limit on rate-of-change alarm, r: low
limit on rate-of-change alarm, T: delay high limit alarm, t: delay low limit
alarm, space: no alarm)

uuuuuu

Unit information (six characters, left-justified)
mV____:

mV

V_____:

V

^C____:

°C

xxxxxx:

(User-defined character string)

f

Sign (+, –)

5.2 Text Data Output Format