beautypg.com

Alarm summary – Yokogawa Button Operated MV2000 User Manual

Page 138

background image

5-20

M-4662

Alarm Summary

• The MV returns the alarm summary in response to an FL command.
• The MV retains a maximum of 1000 alarm events.
Alarm events that exceed 1000 are cleared from the oldest ones.

• Syntax

EACRLF
yy/mo/dd_hh:mm:ss_kkk_ccc_ls_nnnnnnnnnnCRLF
···································
ENCRLF

yy/mo/dd hh:mm:ss

Time when the alarm occurred

yy

Year (00 to 99)

mo

Month (01 to 12)

dd

Day (01 to 31)

hh

Hour (00 to 23)

mm

Minute (00 to 59)

ss

Second (00 to 59)

kkk

Alarm cause

OFF:

Alarm release

ON:

Alarm occurrence

ACK:

Alarm acknowledge

ccc

Measurement, computation, or external input channel number

l

Alarm level (1 to 4)

s

Alarm type (H, h, L, l, R, r, T, or t)

nnnnnnnnnn

Alarm sequence

_

Space

For all-channel alarms, the channel number, alarm level, and alarm status items

are all set to asterisk.

• Example

EA
01/05/11 12:20:00 ON 001 1L

1

01/05/11 12:30:00 OFF 131 3t

2

01/05/11 12:31:00 OFF *** **

2

01/05/11 12:32:00 ACK

4

EN

5.2 Text Data Output Format