3-8
M-4662
3.3
Configuring the Serial Interface
◊ Press MENU and then select Menu tab > Basic setting mode > Menu tab >
Communication (Serial) > Basic settings
For RS-232
• Baud rate
Select 0, 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
• Data length
Select 7 or 8 (bits). To output the data in binary format, select 8.
• Parity
Set the parity to Odd, Even, or None.
• Handshaking
Select Off:Off, XON:XON, XON:RS, or CS:RS.
• Address
Enter a value in the range of 1 to 99 for the Modbus protocol. For a general purpose
communication protocol, do not set this value.
• Protocol
Select Standard for a general purpose communication protocol, Modbus for Modbus
slave, and Master-M for Modbus master.
If you select Modbus master, you must specify Modbus master settings. See section 3.5
for details.
For RS-422/485
• Baud rate
Select 0, 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
• Data length
Select 7 or 8 (bits). To output the data in binary format, select 8.
• Parity
Set the parity to Odd, Even, or None.
• Handshaking
Do not set.
• Address
Select a number from 1 to 99.
• Protocol
This is the same as with the RS-232.