Sets the display update interval

and auto-save interval

Syntax

SW p1,p2,p3,p4
p1

1

p2

Waveform type (T-Y)

p3

Display update interval (5S, 10S, 15S, 30S,

1MIN, 2MIN, 5MIN, 10MIN, 15MIN, 20MIN,
30MIN, 1H, 2H, 4H, 10H)

p4

Auto-save interval (10MIN, 20MIN, 30MIN,

1H, 2H, 3H, 4H, 6H, 8H, 12H, 1DAY, 2DAY,
3DAY, 5DAY, 7DAY, 10DAY, 14DAY, 31DAY)

Query

SW?

Description • You cannot execute this command while the

MV is measuring.

• The selectable auto-save interval (p4) varies

depending on the display update interval (p3)
setting. For details, see the RD-MV1000/RD-
MV2000 User’s Manual
.

• You can specify the data update intervals (p3)

5S and 10S only on high-speed input models
(RD-MV1004, RD-MV1008, and RD-MV2008).
You can specify 15S on medium-speed input
models set to fast sampling mode and high-
speed input models.

• Set the data update interval (p3) to an interval

slower than the scan interval.

• The p4 setting is valid when the saving

method to the external storage medium is set
to auto with the XM command (p1 in the XM
command set to AUTO).

• Set the trend update interval with the NR

command after setting the data update interval
and auto save interval with the SW command.

• The data update interval (p3) can only be set

to an interval slower than the scan interval.
(The scan interval is set using p3 in the XV
command.)

• The selectable range of auto save interval (p4)

varies depending on the data update interval
(p3) setting and the number of channels that
is set with the TJ command.

TW

Sets the secondary trend update

rate

Syntax

TW p1
p1

Data update rate (5S, 10S, 15S, 30S, 1MIN,

2MIN, 5MIN, 10MIN, 15MIN, 20MIN, 30MIN,
1H, 2H, 4H, 10H)

Query

TW?

Example

Set the update rate to 2 minutes.
TW2MIN

Description • Set the data update interval (p1) to an interval

slower than the scan interval.

• You can specify the data update intervals (p1)

5S and 10S only on high-speed input models
(RD-MV1004, RD-MV1008, and RD-MV2008).
You can specify 15S on medium-speed input
models set to fast sampling mode and high-
speed input models.

TM

Sets manual sampling.

Syntax

TM p1,p2,p3
p1

Manual sampling channel number

p2

Enable/Disable (ON, OFF)

p3

Measurement, computation, or external

input channel number

Query

TM[ p1]?

Example

Assign measurement channel 002 to manual
sampling number 001.
TM001,ON,002

Description • You can execute this command on models

with the /MC1 external input channel option.

• You can assign a computation channel on

models with the /M1 math option.

TE

Sets sampling conditions of the

event data

Syntax

TE p1,p2,p3,p4,p5,p6
p1

1

p2

Sample rate (25MS, 125MS, 250MS,

500MS, 1S, 2S, 5S, 10S, 30S, 1MIN, 2MIN,
5MIN, 10MIN)

p3

Sample mode

FREE

Starts data acquisition at memory
start and stops data acquisition at
memory stop.

SINGLETRIGGER

Acquires data for a specified time
once after a trigger occurs and
stops.

REPEATTRIGGER

Acquires data for a specified time
after a trigger occurs and waits for
the next trigger.

p4

Sample time (10MIN, 20MIN, 30MIN, 1H,

2H, 3H, 4H, 6H, 8H, 12H, 1DAY, 2DAY,
3DAY, 5DAY, 7DAY, 10DAY, 14DAY, 31DAY)

p5

Pre-trigger length (0, 5, 25, 50, 75, 95, 100)

percent

p6

Key trigger source ON/OFF

Parameters p5 to p6 are valid when p3 is set to
SINGLETRIGGER or REPEATTRIGGER.

Query

TE[ p1]?

Example

Acquire data at a sampling rate of 125-ms over
10 minutes using a single trigger.
TE1,125MS,SINGLETRIGGER,10MIN

Description You cannot specify a sampling rate that is faster

than the scan interval.

4.4 Setting Commands (Setting)