Yokogawa Button Operated DX2000 User Manual
Page 81
2-12
IM 04L42B01-01E
• Status Relay Details
Press
MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic
setting mode), and select the
Menu tab > Status Relay > Status Relay Details.
Setup Items
• Relay Action > Fail Relay, Status Relay (Release numbers 4 and later)
On DXs without the /AS1 advanced security option
Setting
Description
Fail
Outputs a fail relay.
Status relay
Outputs a status relay. Even if you set both relays to “Status relay,” you
cannot make them output different statuses.
On DXs with the /AS1 advanced security option
Setting
Description
Fail
Outputs a fail relay.
Status relay
Outputs a status relay. Even if you set both relays to “Status relay,” you
cannot make them output different statuses.
Mem. sample*
Relay output continues from memory start until memory stop.
Invalid user
Relay output continues from when a user is determined to be invalid until
a Locked ACK command is executed.
Login
Relay output occurs whenever a user is logged in.
* When the multi batch function (/BT2 option) is being used, relay output starts when memory
start occurs for any of the batches, and relay output stops when memory stop occurs for all
the batches.
• Status Relay Details > Memory/Media status
On: The status of the internal memory and the CF card is relayed.
• Status Relay Details > Measurement error
On: A relay signal is output when a measurement error occurs.
• Status Relay Details > Communication error
On: A relay signal is output when a communication error occurs.
• Status Relay Details > Memory stop
On: A relay signal is output when memory sampling stops.
* When the multi batch function (/BT2 option) is being used, relay output starts when
recording stops for all the batches.
2.9 Outputting the DX Status via the Relay Contact (/F1 and /F2 Options)