App index dc/ac 24 v power supply (/p1) – Yokogawa Button Operated DX2000 User Manual
Page 335
13-17
IM 04L42B01-01E
Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
App
Index
DC/AC 24 V Power Supply (/P1)
Item
Specifications
Rated supply voltage
24 VDC and 24 VAC (50/60Hz)
Allowable power supply voltage range
21.6V to 26.4 VDC/AC
Insulation resistance
Between power terminal and earth: 20 MΩor greater at 500 VDC.
Withstand voltage
Between power terminal and earth: 500 VAC at 50/60 Hz for one minute
Rated power supply frequency (for AC)
50/60 Hz
Allowable power supply frequency range (for AC)
50 Hz±2%, 60 Hz±2%
Power supply fluctuation (for AC)
With variation within 21.6 to 26.4 VDC/AC: ±1digit or less
With variation of ±2 Hz from rated power supply frequency (at 24 VAC): ±(0.1% of rdg+1digit) or
less
Rated power consumption
45 VA (for DC), 70 VA (for AC)
Power consumption
Supply voltage
LCD backlight off
Normal
Maximum
24 VDC
12 VA
20 VA
45 VA
24 VAC (50/60Hz)
20 VA
34 VA
70 VA
Multi Batch Function (/BT2; release number 3 or later)
Item
Specifications
Function
Individual recording start/stop and file generation operations can be performed for each batch.
Equippable models: DX2010, DX2020, DX2030, DX2040, and DX2048
Number of batches
2 to 12
Batch single operations
Recording start/stop, computation reset, message write
Batch overview operations
Computation start/stop, report start/stop, manual sampling, setup data save/load
Scan interval
Maximum speed of 1 s in normal mode only (same for all batches)
Data type
Display or event data only. Trigger mode cannot be used for event data.
Data recording interval
Same for all batches
Data files
Can be displayed or made into an event data file separately for each batch
Number of display groups
Up to twelve per batch
The maximum number of channels per group is ten.
Channels in a display group are sampled for display or event data.
Timers and match time timers 12 max.
Batch single settings
Group, trip line, file header, data file name, text field, batch number, and lot number
PROFIBUS-DP (/CP1 option; release number 3 or later)
Item
Specifications
Function
A PROFIBUS-DP master device can access internal data in the following ways:
Load measurement channel data
Load computation channel data
Write to communication input data (for up to 32 channels)
Data mapping
Buffer
Description
Maximum Size
Input
Measurement channels are arranged at the start of the buffer. As
many computation channels as can be placed into the buffer are
inserted after the measurement channels.
128 bytes
Output
Up to 32 communication input data values is arranged.
128 bytes
Node address
0 to 125
Interface
PROFIBUS-DP-V0 Slave
Transmission medium
Two dedicated cables (one for each signal line)
Transmission speed/distance 9.6 kbps/1200 m to 12 Mbps/100 m
Terminator
No internal terminator (must be terminated externally)
13.5 Options