beautypg.com

Special data handling – Yokogawa Button Operated DX2000 User Manual

Page 63

background image

1-52

IM 04L42B01-01E

Special Data Handling

This section explains the handling of special data in TLOG computation, CLOG
computation, and reports.

• Power Failure Operation (TLOG and Reports)

If a power failure occurs when the report function is enabled or in the middle of the

TLOG computation, the report operation and TLOG computation resume when the
DX recovers from the power failure. The operation varies depending on whether the
DX recovers from the power failure before or after the time to create a report or TLOG
data.

Time of Recovery

Operation

After the time to create the data

The report or TLOG data is created immediately after the

DX recovers. The measured data up to the time of the

power failure is used. At the time the next report or TLOG

data is created, the data after the recovery is used.

Before the time to create the data After the DX recovers, report or TLOG data is created at

the normal time to create the data. The measured data

excluding the power failure period is used.

• Error Data Handling (TLOG, CLOG, and Reports)

If an error occurs in the channel data, the error data is discarded, and the computation

continues. If all the data are in error, an error results.

The following types of data are considered error data.

• Channels set to skip or Off.
• The measured result on a measurement channels is error (A/D converter failure,

etc.).

• The computed result on a computation channel is error.
• The input of the measurement channel is in a burnout condition.
• The external input channel is Off or there is no data (communication failure, etc.)

• Handling of Overflow Data*

* Refers to over range on a measurement channel, computation overflow on a computation

channel, and over range of an external input channel.

For TLOG, CLOG, and Reports

When the channel data is overflow data, the DX handles the data as follows:

Computation Type

Description

Average value or sum

value

Set the handling to ERROR, SKIP, or LIMIT.
ERROR: Considers the data to be a computation error.
SKIP:

Discards the overflow data and continues the computation.

LIMIT:

Replaces the data with the limit value and continues the

computation.

The limit value is the span upper or lower limit or the scale

upper or lower limit of the channel.

Maximum, minimum,

Maximum – minimum

Set the handling to OVER or SKIP.
OVER:

Computes by using the overflow data.

SKIP:

Discards the overflow data and continues the computation.

For Multiplication and Relation Computation EQ and NE

Computation Type Computation

Computed Result

Multiplication

0*(+Over)

0

0*(–Over)

0

(+Over)*0

0

(–Over)*0

0

.EQ.

(+Over).EQ.(+Over)

0

(–Over).EQ.(–Over)

0

.NE.

(+Over).NE.(+Over)

1

(–Over).NE.(–Over)

1

1.8 Computation and Report Function (/M1 and /PM1 Options)

This manual is related to the following products: