Special data handling – Yokogawa Button Operated DX2000 User Manual
Page 63
1-52
IM 04L42B01-01E
Special Data Handling
This section explains the handling of special data in TLOG computation, CLOG
computation, and reports.
• Power Failure Operation (TLOG and Reports)
If a power failure occurs when the report function is enabled or in the middle of the
TLOG computation, the report operation and TLOG computation resume when the
DX recovers from the power failure. The operation varies depending on whether the
DX recovers from the power failure before or after the time to create a report or TLOG
data.
Time of Recovery
Operation
After the time to create the data
The report or TLOG data is created immediately after the
DX recovers. The measured data up to the time of the
power failure is used. At the time the next report or TLOG
data is created, the data after the recovery is used.
Before the time to create the data After the DX recovers, report or TLOG data is created at
the normal time to create the data. The measured data
excluding the power failure period is used.
• Error Data Handling (TLOG, CLOG, and Reports)
If an error occurs in the channel data, the error data is discarded, and the computation
continues. If all the data are in error, an error results.
The following types of data are considered error data.
• Channels set to skip or Off.
• The measured result on a measurement channels is error (A/D converter failure,
etc.).
• The computed result on a computation channel is error.
• The input of the measurement channel is in a burnout condition.
• The external input channel is Off or there is no data (communication failure, etc.)
• Handling of Overflow Data*
* Refers to over range on a measurement channel, computation overflow on a computation
channel, and over range of an external input channel.
For TLOG, CLOG, and Reports
When the channel data is overflow data, the DX handles the data as follows:
Computation Type
Description
Average value or sum
value
Set the handling to ERROR, SKIP, or LIMIT.
ERROR: Considers the data to be a computation error.
SKIP:
Discards the overflow data and continues the computation.
LIMIT:
Replaces the data with the limit value and continues the
computation.
The limit value is the span upper or lower limit or the scale
upper or lower limit of the channel.
Maximum, minimum,
Maximum – minimum
Set the handling to OVER or SKIP.
OVER:
Computes by using the overflow data.
SKIP:
Discards the overflow data and continues the computation.
For Multiplication and Relation Computation EQ and NE
Computation Type Computation
Computed Result
Multiplication
0*(+Over)
0
0*(–Over)
0
(+Over)*0
0
(–Over)*0
0
.EQ.
(+Over).EQ.(+Over)
0
(–Over).EQ.(–Over)
0
.NE.
(+Over).NE.(+Over)
1
(–Over).NE.(–Over)
1
1.8 Computation and Report Function (/M1 and /PM1 Options)