6 general specifications, General specifications -19, App index – Yokogawa Button Operated DX2000 User Manual
Page 337: Construction, Normal operating conditions, Power supply, Isolation
13-19
IM 04L42B01-01E
Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
App
Index
13.6 General Specifications
Construction
Item
Specifications
Mounting
Flush panel mounting (on a vertical plane) (excluding the desktop type)
Mounting angle
Inclined backward up to 30 degrees from a horizontal plane.
Allowable panel thickness
2 to 26 mm
Material
Case:
Metal plate
Bezel and display cover: Polycarbonate
Color
Case:
Grayish blue green (Munsell 2.0B5.0/1.7 or equivalent)
Bezel:
Charcoal gray light (Munsell 10B3.6/0.3 or equivalent)
Front panel
Water and dust proof: Complies with IEC529-IP65 and NEMA No.250 TYPE 4 (except External
Icing Test) (Style number 2 or later), except for side-by-side mounting
External dimensions
288(W) × 288(H) × 226(D) mm (D: depth from the panel mounting plane)
Weight
DX2004 and DX2010: Approx. 6 kg. DX2008 and DX2020: Approx. 6.3 kg. DX2030: Approx. 6.9
kg, DX2040 and DX2048: Approx. 7.3 kg excluding options
Normal Operating Conditions
Item
Specifications
Supply voltage
90 to 132, 180 to 250 VAC
Power supply frequency
50 Hz ± 2%, 60 Hz ± 2%
Ambient temperature
0 to 50°C
Ambient humidity
20 to 80%RH (at 5 to 40°C), 10 to 50% (at 40 to 50°C)
Vibration
10 to 60 Hz, 0.2 m/s
2
Shock
Not allowed
Magnetic field
400 A/m or less (DC and 50/60 Hz)
Noise
Normal mode (50/60 Hz)
DC voltage
The peak value including the signal must be less than 1.2 times the measuring range.
Thermocouple
The peak value including the signal must be less than 1.2 times the measuring thermal electromotive force.
RTD
50 mV or less
Common mode noise
250 VACrms or less for all ranges (50/60 Hz)
Maximum noise voltage between channels
250 VACrms (50/60 Hz) or less
Mounting position
Can be inclined up to 30 degrees backward. Left and right horizontal.
Warm-up time
At least 30 minutes after power on
Installation location
Indoors
Operating altitude
2000 m or less
Power Supply
Item
Specifications
Rated supply voltage
100 to 240 VAC
Allowable power supply voltage range
90 to 132, 180 to 264 VAC
Rated power supply frequency
50 Hz to 60 Hz
Power consumption
Supply voltage
LCD backlight off
Normal
Maximum
100 VAC
28 VA
42 VA
74 VA
240 VAC
38 VA
54 VA
100 VA
Allowable interruption time
Less than 1 cycle of the power supply frequency
Isolation
Item
Specifications
Insulation resistance Between the Ethernet, RS-422/485, and insulation terminals and earth: 20 MΩ or greater at 500 VDC
Withstand voltage
Between the power terminal and earth:
2300 VAC at 50/60 Hz for one minute
Between the contact output terminal and earth:
1600 VAC at 50/60 Hz for one minute
Between the measurement input terminal and earth: 1500 VAC at 50/60 Hz for one minute
Mutually between measurement input terminals:
1000 VAC (50/60 Hz) for one minute (excluding the
RTD input terminal of DX2010, DX2020, DX2030,
DX2040, and DX2048)
Between the remote input terminal and earth:
1000 VDC for one minute
Between the pulse input terminal and earth:
1000 VDC for one minute
Ground
Grounding resistance: 100 Ω or less