beautypg.com

Yokogawa Button Operated DX2000 User Manual

Page 230

background image

6-10

IM 04L42B01-01E

6.4 Starting/Stopping the Recording and Saving

the Measured data

Start the recording and save the measured data to the external storage medium.
For a description of the function, see section 1.4.

Procedure

• Starting the Recording (Memory Start)

Press

START. The internal memory icon in the status display section changes from

the stop icon to memory sampling icon.
• When recording display data or event data in free mode, recording starts.
• When recording event data in trigger mode, the DX enters the trigger-wait

condition.

* On DXs with the /AS1 advanced security option, recording will not start, even if you press

START in setting mode.

* For the procedures when using the batch function, see section 6.3. If you are using the multi

batch function (/BT2 option), see the DX1000/DX1000N/DX2000 Multi Batch (/BT2) User’s
Manual, IM04L41B01-03E
.

• Applying a Trigger to Start the Recording

Carry out the procedure below when the DX is waiting for a trigger.

Trigger through Key Operation

The procedure below can be carried out when recording event data in trigger mode

and the DX is configured so that the start trigger is applied through key operation.

1.

Press

FUNC.

The

FUNC

key menu appears.

2.

Press the

Trigger soft key.

The recording starts.

Trigger by an Event (Event action function must be configured. See

section 7.1.)

Recording starts when an event occurs.

• Automatically Saving Measured Data

Automatic saving takes place when

Auto save is set to On (see section 6.2 for details).

The save destination is the CF card.
Have the CF card inserted in the slot at all times. While the memory sampling is in

progress, the measured data recorded in the internal memory is automatically saved
to the CF card.

Action when Media FIFO is not enabled: If data storage to the storage medium is not

complete such as due to insufficient free space, the unsaved data is saved the next
time the data is automatically saved.

Saving the Display Data or Event Data during Memory Sampling through

Key Operation

The save destination is the CF card.
This operation can be carried out when recording display data or when recording

event data in

Free mode. Unsaved measured data is saved to the CF card.

1.

In the operation mode, press

FUNC.

The FUNC key menu appears.

2.

Press the

Save display or Save event soft key.

The display data or event data is saved to the CF card.

Time

Saved the previous time

Save operation

File

File

File

Saved this time

This manual is related to the following products: