beautypg.com

Yokogawa Button Operated DX2000 User Manual

Page 32

background image

1-21

IM 04L42B01-01E

Overview of Functions

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Alarm Summary

Displays a list of the most recent alarms.
• Up to 1000 alarms can be displayed.
• You can select arbitrary alarm information and recall the historical trend of the display

data or event data that contains the alarm information.

For the setting procedure, see section 4.6.

To the historical trend display

Number of the alarm information displayed on the bottom line/number of alarm

information in the internal memory

Cursor (selects the alarm)

: Alarm occurrence

( blinks until the alarm ACK operation is carried out if “Indicator” is set to

“Hold.”)

Channels on which alarms are occurring

Alarm level (1, 2, 3, 4)/type (H, L, h, l, R, r, T, t)

Date/Time of alarm occurrence/release

: Alarm release
: Alarm acknowledge

(when blinking is cleared through the alarm ACK operation)

When you use the alarm annunciator function (release number 3 or later), the alarm
occurrence mark follows the annunciator sequence. If the alarm sequence is no lock-in
(ISA-A-4):
• The alarm occurrence mark does not blink.
• “ACK” is recorded when the alarm is released.

1.3 Display

This manual is related to the following products: