Range > type, Range > range, Range > span lower, span upper – Yokogawa Button Operated DX2000 User Manual
Page 100: Range > scale lower, scale upper
3-4
IM 04L42B01-01E
• Range > Type
Input type when
Mode is Delta or Scale. See the description on Mode above.
• Range > Range
Input type details.
Standard
Standard
20mV
–20.000 mV to 20.000 mVDC
60mV
–60.00 mV to 60.00 mVDC
200mV
–200.00 mV to 200.00 mVDC
2V
–2.000 V to 2.000 VDC
6V
–6.000 V to 6.000 VDC
20V
–20.000 V to 20.000 VDC
20V
–50.00 V to 60.00 VDC
Pt
Pt100
JPt
JPt100
Level
ON/OFF(Voltage)
Contact ON/OFF(Contact
1-5V
0.800V to 5.200V
R
Type R
S
Type S
B
Type B
K
Type K
E
Type E
J
Type J
T
Type T
N
Type N
W
Type W
L
Type L
U
Type U
WRe
type WRe
Setting
Input Type
Notes
Setting
Input Type
Notes
Cu10 (GE)
Cu10 (L&N)
Cu10 (WEED)
Cu10 (BAILEY)
Cu10: a = 0.00392 at 20
°
C
Cu10: a = 0.00393 at 20
°
C
Cu25: a = 0.00425 at 0
°
C
Cu1
Cu2
Cu3
Cu4
Cu5
Cu6
Cu25
Setting
Input Type
Notes
/N3
option
/N1
option
Kp
Kp vs Au7Fe
PLATI
PLATINEL
PR
PR40-20
NiMo
NiNiMo
W/WRe W/WRe26
N2
Type N (AWG14)
XK
XK GOST
*1
Pt50
Pt50
Ni1
Ni100 (SAMA)
Ni2
Ni100 (DIN)
Ni3
Ni120
J263
J263*B
Cu53
Cu53
Cu100
Cu100: a = 0.00425 at 0°C
Pt25
Pt25
Pt100G
Pt100 GOST
*1
Cu100G Cu100 GOST
*1
Cu50G
Cu50 GOST
*1
Cu10G
Cu10GOST
*1
Pt46G
Pt46 GOST
*1
Setting
Input Type
Notes
Pt200W
Pt200(WEED)
*2
*1 A function available on DXs with release number 3 or later.
*2 This function is available for release numbers 4 and later.
• Range > Span Lower, Span Upper
Input range. The selectable range is displayed on the screen.
Note
• You cannot set the same value to
Span Lower and Span Upper.
• When the
Mode is 1-5V or Sqrt, Span Lower must be less than Span Upper.
• Range > Scale Lower, Scale Upper
Input range after converting the unit.
The selectable range is from –30000 to 30000. The decimal place is determined by
the
Scale Lower setting. It can be set to the following positions: “X.XXXX,”
“XX.XXX,” “XXX.XX,” “XXXX.X,” or “XXXXX.”
3.3 Setting the Input Range