3-4

IM 04L42B01-01E

• Range > Type

Input type when

Mode is Delta or Scale. See the description on Mode above.

• Range > Range

Input type details.

Standard

Standard

20mV

–20.000 mV to 20.000 mVDC

60mV

–60.00 mV to 60.00 mVDC

200mV

–200.00 mV to 200.00 mVDC

2V

–2.000 V to 2.000 VDC

6V

–6.000 V to 6.000 VDC

20V

–20.000 V to 20.000 VDC

20V

–50.00 V to 60.00 VDC

Pt

Pt100

JPt

JPt100

Level

ON/OFF(Voltage)

Contact ON/OFF(Contact

1-5V

0.800V to 5.200V

R

Type R

S

Type S

B

Type B

K

Type K

E

Type E

J

Type J

T

Type T

N

Type N

W

Type W

L

Type L

U

Type U

WRe

type WRe

Setting

Input Type

Notes

Setting

Input Type

Notes

Cu10 (GE)

Cu10 (L&N)

Cu10 (WEED)

Cu10 (BAILEY)

Cu10: a = 0.00392 at 20

°

C

Cu10: a = 0.00393 at 20

°

C

Cu25: a = 0.00425 at 0

°

C

Cu1

Cu2

Cu3

Cu4

Cu5

Cu6

Cu25

Setting

Input Type

Notes

/N3

option

/N1

option

Kp

Kp vs Au7Fe

PLATI

PLATINEL

PR

PR40-20

NiMo

NiNiMo

W/WRe W/WRe26

N2

Type N (AWG14)

XK

XK GOST

*1

Pt50

Pt50

Ni1

Ni100 (SAMA)

Ni2

Ni100 (DIN)

Ni3

Ni120

J263

J263*B

Cu53

Cu53

Cu100

Cu100: a = 0.00425 at 0°C

Pt25

Pt25

Pt100G

Pt100 GOST

*1

Cu100G Cu100 GOST

*1

Cu50G

Cu50 GOST

*1

Cu10G

Cu10GOST

*1

Pt46G

Pt46 GOST

*1

Setting

Input Type

Notes

Pt200W

Pt200(WEED)

*2

*1 A function available on DXs with release number 3 or later.
*2 This function is available for release numbers 4 and later.

• Range > Span Lower, Span Upper

Input range. The selectable range is displayed on the screen.

Note

• You cannot set the same value to

Span Lower and Span Upper.

• When the

Mode is 1-5V or Sqrt, Span Lower must be less than Span Upper.

• Range > Scale Lower, Scale Upper

Input range after converting the unit.
The selectable range is from –30000 to 30000. The decimal place is determined by

the

Scale Lower setting. It can be set to the following positions: “X.XXXX,”

“XX.XXX,” “XXX.XX,” “XXXX.X,” or “XXXXX.”

3.3 Setting the Input Range