beautypg.com

Chapter 1 overview of functions, 1 input section, Input section -1 – Yokogawa Button Operated DX2000 User Manual

Page 12: App index, Measurement channel, Input type and computation

background image

1-1

IM 04L42B01-01E

Overview of Functions

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

1.1 Input Section

Measurement Channel

• Number of Measurement Channels and Scan Interval

The DX samples the input signals on the measurement channels at the scan interval

to obtain the measured values. The table below shows the relationship between the
number of measurement channels and the scan interval.

DX2004
DX2008
DX2010
DX2020
DX2030
DX2040
DX2048

25 ms

125 ms

125 ms

250 ms

2 s, 5 s

4
8
10
20
30
40
48

Fast Sampling Mode*

Normal Mode

Number of

Measurement

Channels

Model

Scan Interval

Integration time of the A/D

converter

60 Hz/50 Hz/100 ms

60 Hz/50 Hz

600 Hz (fixed)

* Not available on models equipped with external input channels (/MC1 option) or

when the multi batch function (/BT2 option) is being used.

1 s, 2 s, 5 s

For the setting procedure, see section 3.1.

• Integration Time of the A/D Converter

The DX uses an A/D converter to convert the sampled analog signal to a digital

signal. By setting the integration time of the A/D converter to match the time period
corresponding to one cycle of the power supply or an integer multiple of one cycle, the
power supply frequency noise can be effectively eliminated.

• Because 100 ms is an integer multiple of 16.7 ms and 20 ms, this setting can be used to

eliminate the power frequency noise for both frequency, 50 Hz and 60 Hz.

• In fast sampling mode, the performance of eliminating power frequency noise is worse than

in normal mode. We recommend that you use normal mode when making measurements in
an environment affected by power frequency noise.

For the setting procedure, see section 3.1.

Input Type and Computation

You can make measurements using the following input types.

*1 Item sold separately. For example, a 250-Ω shunt resistor is used to convert the signal

to 1 to 5 V for 4-20 mA input.

*2 /N3 option.

*3 /N1 option.

*4 /PM1 option.

Input Type

Description

DC voltage

Measures a DC voltage in the range of ±20 mV to ±50 V.

DC current

A shunt resistor*

1

is attached to the input terminal. The current signal is converted

to a voltage signal and measured. The measurable range is the range equivalent

to the “DC voltage” range indicated above after converting the current to the

voltage signal.

Thermocouple Measures temperature corresponding to each type: R, S, B, K, E, J, T, N, W,

L, U, and WRe3-25. Measurement is possible on other thermocouples

such as PR40-20 and PLATINEL*

2

.

RTD

Measures temperature corresponding to each type: Pt100 and JPt100.

Measurement is possible on other RTDs such as Cu10 or Cu25*

3

and Pt50 or

Ni100*

2

.

ON/OFF input Displays the contact input or voltage input signals by correlating them to 0% or

100% of the display range.

Contact input: Closed contact is ON (1). Open contact is OFF (0).

Voltage input: Less than 2.4 V is OFF (0). Greater than or equal to 2.4 V is ON (1).

Pulse input*

4

Counts the pulses.

Chapter 1

Overview of Functions

This manual is related to the following products: