3 event notification, 3 event, Notifi cation -7 – Yokogawa digitalYEWFLO (DY) User Manual
Page 79: E. burst mode, 3 event notifi cation, 1) set event notifi cation, A) event mask, C) event notifi cation control, 2) acknowledge event notifi cation (dtm), A) get event number

<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-7
IM 01F06A00-01EN
e. Burst Mode
When the Burst mode is set to Wired HART
Enabled, the device starts to send the data.
• Procedure to call up the display
[Root Menu]
→ Detailed setup → Confi gure
outputs
→ HART output → Burst condition → Burst
Message1, 2 or 3
→ Burst mode → Wired HART
Enabled
9.10.3 Event Notifi cation
When a setting change and a change of the Self-
diagnostics occur, device detect it as an event and
can transmit an alarm signal continuously.
Alarm contained in the following item can be set to
Event, and can be detected.
• Device
Status
• Status group 1 to 3
• Ext dev status
• Device diagnostic status 0
Up to four events that occurred can be stored.
When using this function, set to Burst mode as
“Wired HART Enabled”.
(1) Set Event Notifi cation
• Procedure to call up the display
DD (HART 7)
DTM (HART 7)
[Root Menu]
→ Detailed setup →
Confi gure outputs
→ HART output →
Event Notifi cation
→ Event
Notifi cation
Control
Stop the event monitor: OFF
Shift to the monitor state:
Enable event notifi cation on token-
passing data
link layer
→ Event Mask
Set the status to detect
→ Event
Notifi cation
Retry Time
Set the retry time when the event occur.
→ Max Update
Time
Set the retry time when the event does
not occur.
→ Event Debounce
Interval
The setting of the minimum event
duration
a) Event Mask
Set the status to detect in the Event Mask
parameter.
Device Status Mask
Status group 1 to 3
Ext dev status Mask
Device Diagnostic Status 0 Mask
b)
Event Notifi cation Retry Time/ Max
Update Time/ Event Debounce Interval
Set to Event Notifi cation Retry Time, Max
Update Time and Event Debounce Interval.
For Event Noteifi cation Retry Time, set the
value thet is smaller than Max Update Time.
Event Notifi cation Retry
Time/Max Update Time
Event Debounce Interval
—
Off
0.5 s
0.5 s
1 s
1 s
2 s
2 s
4 s
4 s
8 s
8 s
16 s
16 s
32 s
32 s
1 min
1 min
5 min
5 min
10 min
10 min
15 min
15 min
30 min
30 min
45 min
45 min
60 min
60 min
c) Event Notifi cation Control
Select “Enable event notifi cation on token-passing
data link layer” in the Event Notifi cation Control
parameter to shift to the monitor state:
(2) Acknowledge Event Notifi cation (DTM)
The transmission of the event message stops
when event is approved.
• Procedure to call up the display
DTM (HART 7)
[Root Menu]
→ Detailed setup →
Confi gure outputs
→ HART output →
Event Notifi cation
→ Knowledge →
→ Acknowledge
Event
Notifi cation
Acquisition of the event number and
approval.
a) Get Event Number
Confi rm the latest event number.
Execute Acknowledge Event Notifi cation
method.
1) Set “0” to enter Event Number.
2) OK.
3) Set “Trans 0: Read Event Notifi cation” to
Select Transaction.
4) OK.
5) Confi rm Event Number.