<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>

8-4

IM 01F06A00-01EN

8.10.2 Multidrop Mode

“Multidropping” devices refers to the connection
of several devices to a single communications
transmission line. Up to 15 devices can be
connected when set in the multidrop mode. To
activate multidrop communication, the device
address must be changed to a number from 1 to
15. This change deactivates the 4 to 20 mA analog
output, sending it to 4 mA. The alarm current is also
disabled.
(1) Polling address

• Procedure to call up the display

DD (HART 5)

[Root Menu]

→ Detailed setup →

Confi gure outputs

→ HART output →

DTM (HART 5)

Confi guration

→ HART →

→ Poll addr

Enter the number from 1 to 15

(2) Enabling the Multidrop Mode

About the procedure to call up the Polling
display, please refer to the User’s Manual of
each confi guration tool.

NOTE

When the same polling address is set for two or
more devices in multidrop mode, communication
with these devices are disabled.

(3) Communication when set in multidrop mode.

• The HART confi guration tool seaches for a

device that is set in multidrop mode when it is
turned on. When the HART confi guration tool
is connected to the device, the polling address
andthe tag will be displayed.

• Select the desired device. After that, normal

communication to the selected device is
possible. However, the communication speed
will be slow.

To release multidrop mode, call up the Poll addr
display and the address to “0”.

8.10.3 Switching HART Protocol Revision

When the output signal code is “-J”, HART protocol
revision of device can be selectable from 5 or 7.
The HART protocol revision is set and shipped as
specifi ed in the order.
To change the HART protocol revision after
shipment, follow the procedure shown below.

IMPORTANT

When change the protocol revision, confi rm the
items below.

• Protocol revision supported by HART

confi guration tool must be the same or
higher than new protocol revision of the
device. (Refer to Section 8.1 “HART Protocol
Revision”)

• Confi rm that the DD or DTM which is suitable

to new protocol revision of device is installed
in the confi guration tool. (Refer to Section
8.1 “HART Protocol Revision” and Section
8.2 “HART Confi guration Tool and Matching
of Device Revision”)

(1) Call up the parameter for protocol

revision change

• Call up the parameter for protocol revision

change Procedure to call up the Chng
universal rev
display.

[Root Menu]

 Detailed setup  Device

information

 Revision numbers  Chng

universal rev

(2) Active the parameter for protocol

revision change

• Active the “Chng universal rev” method

IMPORTANT

The message is displayed to separate the device
from the automatic control loop.
Confi rm that the device is separated.

(3) Set the protocol revision number

Input the new revision number
An input column for new protocol revision
number is displayed.
Input the new HART protocol revision number
of “5” for HART 5 or “7” for HART 7.
Confi rm the revision number in the ‘Next
universal rev’.
[Root Menu]

→ Detailed setup → Device

information

 Revision numbers  Next

universal rev

(4) Applying the new protocol revision

a. Close the confi guration tool

After completion of Chng universal rev

method, close the HART confi guration tool.