<6. PARAMETERS>

6-20

IM 01F06A00-01EN

Indication

Diagnostic

Message

Error Name

Problem Cause

Current Output

% Output

Pulse

Output

Engineering

Unit Output

Totalizing

Output

Engineering

Temp Output

Pulse / Status Output

How to recover

Select

fl ow

rate

Select

temperature

Select

fl ow

rate

Select

temperature

Pulse

(*2)

Status

(*2)

Alarm

(*2)

Err-01

FLOW

OVER

OUTPUT

Over range

output

signal

Output signal is

110% or more

(*1)

Fixed at

110%

(*1)

Normal

Operation

Fixed at

110%

(*1)

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

OFF(H)

Change

parameters or

over ranged

fl ow

input

Err-02

SP

AN

SET

ERROR

Span Setting

Error

Span setting

parameter is more

than 1.5 times of

max

fl ow

velocity

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

OFF(H)

Change

parameters span

factor is outside the

acceptable limits

Err-06

PULSE

OUT

ERROR

Pulse output

error

Pulse output

frequency is more

than 10kHz

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Fixed at

10KHz

Normal

Operation

Normal

Operation

Normal

Operation

Fixed at

10kHz

Change

parameters

(ItemC,ItemE)

Err-07

PULSE

SET

ERROR

Pulse setting

error

Pulse output

frequency setting is

more than 10kHz

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Change

parameters

(ItemC,ItemE)

CHECK

V

ibration

T

ransient

noise

Error of

V

ibration

T

ransitional

disturbance

Hold

Normal

Operation

Hold

Normal

Operation

Normal

Operation

Hold

Normal

Operation

Normal

Operation

Hold

Hold

OFF(H)

CHECK

the

vibration

CHECK

V

ibration

High

vibration

Error of

V

ibration

High vibration

Based on

K45

Normal

Operation

Based on

K45

Normal

Operation

Stop Output

Based on

K45

Stop the total

Normal

Operation

Normal

Operation

Normal

Operation

OFF(H)

CHECK

the

vibration

CHECK

Flow

Fluctualing

Error of Flow

Fluctuating

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

OFF(H)

CHECK

the

clogging

CHECK

Flow

Clogging

Error of Flow

Clogging

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

OFF(H)

CHECK

the

clogging

Err-10

(*3)

TEMP

OVER

OUTPUT

Over range

Temp output

signal

Temp output signal

is 1

10% or more,

and 0% below

.

Normal

Operation

Fixed at 1

10%

in case of over

110%, and

fi xed

at 0% when

in case of less

than 0%.

(*1)

Normal

Operation

Fixed at 1

10%

in case of over

110%, and

fi xed

at 0% when in

case of less than

0%.

(*1)

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

OFF(H)

CHECK

the

temperature

or temperature

span

Err-1

1

(*3)

OVER

TEMP

Error of

temperature

Temp value is -50°C

below or 300°C

over

.

Remain in

operationat

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

Remain in

operationat

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

Remain in

operation at

Temp=-50°C or

Temp=300°C

OFF(H)

CHECK

the

temperature

Err-12

(*3)

TEMP

SENSOR

FAUL

T

Error of

thermometer

Disconnection

or short of

thermometer sensor

Remain in

operation

at Manual

setting

condition

Based on F58

Remain in

operation

at Manual

setting

condition

Based on F58

Remain in

operation

at Manual

setting

condition

Remain in

operation

at Manual

setting

condition

Remain in

operation

at Manual

setting

condition

Based on

F58

Remain in

operation

at Manual

setting

condition

Remain in

operation

at Manual

setting

condition

OFF(H)

Change

thermometer

sensor

.

Err-13

(*3)

TEMP

CONV

.

FAUL

T

Error of

temperature

converter

Temperature

converter is failed

Remain in

operation

at Manual

setting

condition

Based on F58

Remain in

operation

at Manual

setting

condition

Based on F58

Remain in

operation

at Manual

setting

condition

Remain in

operation

at Manual

setting

condition

Remain in

operation

at Manual

setting

condition

Based on

F58

Remain in

operation

at Manual

setting

condition

Remain in

operation

at Manual

setting

condition

OFF(H)

Change

converter

case build in

temperature

sensor

.

Err-20

PRE-AMP

ERROR

PRE-AMP

is

failed

Normal

Operation

Remain in

operation at

Manual Setting

Temperature

Value

Normal

Operation

Remain in

operation at

Manual Setting

Temperature

V

alue

Normal

Operation

Normal

Operation

Normal

Operation

Remain in

operation at

Manual Setting

Temperature

Value

Normal

Operation

Normal

Operation

OFF(H)

Replace

the

AMP

. unit

Err-30

EE

PROM

ERROR

EEPROM

is not

functioning

correctly

Over 1

10%

or -2.5%

below

Over 1

10% or

-2.5% below

Fixed at 0%

Fixed at 0%

Halt

Fixed at 0%

Halt

Fixed at 0%

Stop the

Output

OFF(H)

OFF(H)

Replace

the

AMP

. unit

Err-40

FLOW

SEBSOR

FAUL

T

Error of Flow

sensor

Flow sensor Is fauit.

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

Normal

Operation

OFF(H)

Change

Flow

sensor

CPU F

AUL

T

CPU is

failed

All operations are

Dead. Display and

self dignostic function

is also dead.g

Over 1

10%

or -2.5%

below

Over 1

10% or

-2.5% below

Halt

Halt

Halt

Halt

Halt

Halt

Halt

Halt

Halt

Replace

the

AMP

. unit

Note. Normal Operation : Operation continues without relation to error occurrence.

Remain in Operation : Calculation continues with relation to error occurrence.

(*1): “1

10%” is based on “D30 : OUT

LIMIT(H)”.

(*2):

Pulse output

: These conditions should be done in case of which B20 is “SCALED PULSE”, “UNSCALED PULSE”, “FREQUENCY”.

Status output :

These conditions should be done in case of which B20 is “FLOW SW (LOW :ON)”, “FLOW SW (LOW : OFF)”.

Alarm output

: These conditions should be done in case of which B20 is “Alarm”.

(*3): Only for /MV

6.5 Self-Diagnostic (Error Code List)

When an ERROR is displayed by SELF CHECK in item A60, B60, C60, D60, E60, H60, J60, K60 or M60,
press function key F2 [DIAG] and the error contents are displayed.