background image

ATRT-03 S2, ATRT-03A S2, AND ATRT-03B S2 USER’S MANUAL

REV 2

35

d. The following screen will be displayed:

Press the

[START]

key to initiate the test.

e. The following screen will be displayed while the test is being performed:

The test results will be displayed on the LCD screen when testing has finished:

The polarity is displayed as either a plus sign (+) for “in-phase” or a minus sign (-) for
“out-of-phase”. The value listed under “% DIFF” is the percentage error.

NOTE

The percentage error (% DIFF) is calculated as the absolute value of:
[(Calculated Ratio – Measured Ratio) / Calculated Ratio)] x 100

Press any key to continue.

If using an ATRT-03 S2 or ATRT-03A S2, continue to step f.

If using an ATRT-03B S2, continue to step h.

RATIO

m

A

%DIFF

+10.004 0004 0.04