Vanguard ATRT-03_03B S2 User Manual
Page 40

ATRT-03 S2, ATRT-03A S2, AND ATRT-03B S2 USER’S MANUAL
REV 2
35
d. The following screen will be displayed:
Press the
[START]
key to initiate the test.
e. The following screen will be displayed while the test is being performed:
The test results will be displayed on the LCD screen when testing has finished:
The polarity is displayed as either a plus sign (+) for “in-phase” or a minus sign (-) for
“out-of-phase”. The value listed under “% DIFF” is the percentage error.
NOTE
The percentage error (% DIFF) is calculated as the absolute value of:
[(Calculated Ratio – Measured Ratio) / Calculated Ratio)] x 100
Press any key to continue.
If using an ATRT-03 S2 or ATRT-03A S2, continue to step f.
If using an ATRT-03B S2, continue to step h.
RATIO
m
A
%DIFF
+10.004 0004 0.04
test in progress
please wait...
"START" TO TEST
OR
"STOP" TO ABORT