beautypg.com

Vanguard ATRT-03_03B S2 User Manual

Page 120

background image

ATRT-03 S2, ATRT-03A S2, AND ATRT-03B S2 USER’S MANUAL

REV 2

115

The unit will then proceed to perform a Y to Y test. The following screen will be
displayed momentarily:

The screen will then be updated with the test results for each phase:

The following screen will be displayed when testing is finished:

NOTE

The ratio reading should be 1.0000 ±0.1% for all tests.

Press any key to return to the “START-UP” menu.

TEST RESULTS

RATIO mA %DIFF
A +1.0000 0001
B +1.0000 0001
C +1.0000 0001

TEST COMPLETE

TEST RESULTS

RATIO mA %DIFF
A +1.0000 0001
B +1.0000 0001
C +1.0000 0001

XFMR TYPE: YN

yn0

Y TO Y TEST





TEST RESULTS

RATIO mA %DIFF
A +1.0000 0001
B +1.0000 0001
C +1.0000 0001

XFMR TYPE: D

d0

This manual is related to the following products: