Common Problems and Recommended Actions

z I/O Signals Cannot Be Sent or Received to/from the PLC.

Cause:

[1] The 24-V I/O power supply is connected in reverse polarities.

(In this case, input circuits are not affected, but output circuits will be damaged.)

[2] If an output circuit presents this problem, electrical current exceeding the maximum current flowed

due to a large load and a circuit component was damaged.

[3] Poor contact at the connector or relay terminal block on the PLC side.
[4] The female pins on the flat cable connector are bent outward, thus causing contact failure with the

male pins on the controller connector.

Action:

Check the connection condition of the power supply and connector, as well as the load on the output
side.
If [1] or [2] is suspected, the controller must be replaced. If [4] is likely, the flat cable must be replaced.
Either way, contact IAI.

Caution:

When checking the continuity of the shield cable, exercise due caution not to bend the female pins
on the connector outward. It may cause contact failure, resulting in malfunction.

z The ALM Lamp Illuminates after the Power Is Turned On.

(An alarm is present, emergency stop is actuated, or the motor power is cut off.)
* If the ALM output signal is OFF, an alarm is present. Connect a PC or teaching pendant to check the nature of

the error and remove the cause.

* If the ALM output signal is ON, the emergency stop circuit is actuated.
Check the following items:
[1] Is the emergency stop switch on the operation panel pressed by mistake? Is the necessary interlock canceled?
[2] Is the emergency stop switch on the teaching pendant pressed by mistake?
[3] If multiple controllers are linked together, are they wired correctly?

z After Turning On the Power, the SV Lamp Does Not Illuminate upon Servo-on Signal Input.

(The Servo Does Not Turn On.)
Cause:

[1] Inappropriate contact of the shield cable
[2] Faulty controller

Check the servo-on signal (SON) in the I/O monitor screen on the PC or teaching pendant.
If the signal is input, the controller may be faulty. Contact IAI.

[3] Check if parameter No. 42 [Enable function] is set to “Enable” by mistake by connecting a teaching

pendant not supporting the enable switch.