background image

31

4. Operation Using I/O Signals

4. Operation Using I/O Signals

This chapter explains the wire connections and operation timings you should know in order to perform positioning
operation using a PLC with I/O signals. Two PIO patterns are available for you to choose from in accordance with your
specific application.

PIO pattern

Setting (User Parameter No. 25)

Standard mode (factory setting)

0

Push mode

1

4.1 Interface

Circuit

The standard interface circuit conforms to the NPN specification, but the PNP specification type is also available as an
option.
To simplify wiring, a common power line is used for both the NPN specification and PNP specification. Accordingly you
need not reverse the power connections when using the PNP specification.

4.1.1

External Input Specifications

Item Specification

Number of input points

4 points

Input voltage

24 VDC

r 10%

Input current

5 mA per circuit

Operating voltage

ON voltage:

Min. 18 V (3.5 mA)

OFF voltage: Max. 6 V (1 mA)

Leak current

Max. 1 mA per point

Insulation method

Photocoupler

Internal circuit configuration

[NPN specification]

[PNP specification]

Controller

Controller

+24-V external

power supply

+24-V external

power supply

Each

input

Each

input

Internal circuit

Internal circuit