beautypg.com

Ransburg, Setup and adjustments, Rcs-2 user manual - appendix – Ransburg RCS 2 Ratio Control System User Manual

Page 61

background image

Since all catalysts are not the same and have

differing abilities to remove heat from this se sor,

the sensor must be calibrated prior to use.

Setup and Adjustments

Refer to the System Interconnect Diagrams in

the Maintenance/Troubleshooting manual before

proceeding with any of the following setup and

adjustment procedures.

Access the Digital/Analog I/O screen on the User

Interface Screen of the RCS-2. Select the Analog

I/O option. On this screen, the current coming

from the analog output amplifier can be monitored.

1. Fill the system to be monitored with the fluid

to be monitored (NOTE: YOU CANNOT USE AIR

AS THE FLUID!)

2. Monitor the output current from analog output

amplifier (P/N: 22-1050) on the User Interface

Analog I/O Screen.

3. Let the fluid stand in the line (NO Fluid Flow)

for a minimum of 60 seconds. (The longer you

can let the fluid stand, the better the accuracy

and response time of the Flow Monitor System.)

4. Make sure the switch on the control amplifier

(P/N: 22-1046) is set to position 1 (LIQUID).

User Interface Parameter Setup

There are three parameters that must be pro-

grammed for this feature to work correctly.

Hardener Flow On – This is the level (in milli-

amps) above which the hardener is considered

to be flowing.

Hardener No Flow - This is the level (in milliamps)

below which the hardener is considered as not

flowing.

(The Hardener Flow On parameter must always

be greater than the Hardener No Flow parameter.)

Note that if the current being sensed is between

the Hardener No Flow nad the Hardener Flow

On setpoint, as long as the flow is increasing, the

processor will assume that hardener is flowing.

If the flow being sensed is between these two

values and is not changing or is decreasing, the

processor will assume that there is no hardener

flow.

Hardener Sample Time – This is the time period

of no hardener flow that the hardener no flow timer

should accumulate to before generating a fault.

This time continues to accumulate as long as the

processor sees no hardener flow regardless of the

number of applicator triggers. The timer is reset

every time the flow meets or exceeds the value

programmed in for Hardener Flow On.

The initial setup for these parameters should be

set to the following values: delay time = 4 sec-

onds, no-flow = 6 mA, flow-on = 10 mA. After the

zero flow calibration has been done correctly, the

system can now be programmed to fit

the applica-

tion. The delay time is used to prevent nuisance

hardener flow errors. To properly set this time to

minimize delays and prevent nuisance errors, the

delay time should be set to a value which is less

than the minimum spray-on time of the system

being measured. The delay time is cumulative

to allow for short spray-on times used in some

applications. The smallest difference between the

delay time and the minimum spray-on time should

be 100 mSec. Smaller values can be used, but

>

If the current continues to vary after

you adjust the pot, you have not waited

long enough.

NOTE

5. Adjust the trim potentiometer on the control

amplifier until the output current displayed on

the User Interface Screen is equal to 4.80mA

+/- 0.10mA.

6. This completes the zero flow adjustment of the

hardener no-flow detect system.

RCS-2 User Manual - Appendix

58

LN-9407-00.2

Ransburg