Pump Inlet Pressure

Type of Input: Channel

Type of Signal: Jumper Selectable

Factory Setting: 4-20 mA

This input is typically connected to a pressure

sensor located near the input of the pump. When

used in conjunction with a pilot operated fluid

regulator on the inlet of the pump, it minimizes

the differential pressure across the pump, thereby

increasing the accuracy of the pump.

Pump Outlet Pressure

Type of Input: Channel

Type of Signal: Jumper Selectable

Factory Setting: 4-20 mA

This input is typically connected to a pressure

sensor located near the output of the pump. This

is used to monitor and control the differential

pressure across the pump, thereby increasing

the accuracy of the pump.

This outlet pressure is also used as the feather

pressure for manual spray guns if an optional

feather pressure sensor is not used.

ANALOG OUTPUTS

Most of the analog outputs are jumper selectable

to be 0 to 10 VDC or 4-20 mA. Actual Flow, how-

ever, is fixed at 0-10 VDC.

Motor Speed

Type of Output: Channel

Type of Signal: Jumper Selectable

Factory Setting: 0-10 VDC

This output is connected to the analog input on

the servo motor controller located in the motor

amplifier panel. A 0 VDC signal tells the servo

controller to run at 0 RPM, a 10 VDC signal tells

it to run at the programmed maximum RPM for

that pump.

Pressure Control

Type of Output: Channel

Type of Signal: Jumper Selectable

Factory Setting: 0-10 VDC

This output is normally connected a voltage to

pressure transducer which converts a 0 to 10

VDC signal to a 0 to100 psi air pressure. The

pressure is then used to control the pilot port on

a fluid regulator. This fluid regulator is then used

to control the fluid inlet pressure of the pump.

Actual Flow

Type of Output: Gun

Type of Signal: 0-10 VDC

This output is 0 to 10 VDC output that is propor-

tional to the actual flow of material coming out

of the applicator. 0 VDC means no flow and 10

VDC indicates 2000 cc/min. (Therefore, 3.40 VDC

would indicate 680 cc/min.)

FREQUENCY INPUTS

All frequency inputs are optically isolated and

expect a maximum amplitude square wave of

24 VDC and a maximum frequency of 1.5 KHz.

Both sides of the optical isolators are accessible,

allowing the RCS-2 to sink or source any of the

frequency signals.

Motor Feedback

Type of Output: Channel

Type of Signal: Frequency

This signal is a square wave output from the servo

motor controller, indicating the actual speed of the

motor that is driving the pump. It is used by the

firmware to determine the current flow rate of the

material out of the pump. (It can alternately be

connected to the output of a flow meter placed in

the fluid stream.)

Solvent Flowmeter

Type of Output: Gun

Type of Signal: Frequency

This input allows users to connect a flowmeter

in the solvent supply line and collect totalization

data on solvent usage.

RCS-2 User Manual - Installation