Quickstart, English – Burkert Type 8175 User Manual
Page 75
7
8175
ENGLISH
QUICKSTART
To access the CALIBRATION MENU simutaneously press for
ENTER
5 seconds.
-
The ‘Enter‘ key can be locked to avoid accidental or unauthorised access - section 3.3.
-
Reference can additionally be made to the menu guide - section 4.2.
2.2.2
Programming - Level
The actions which are highlighted in grey
must be fully completed for accurate
measurement.
Choose filters 0-2 if no echo filtering
of obstructing obstacles is required
and filters 3-9 if echo filtering is
required.
331.4 m/s within the air with a devia-
tion of 0.59m/s/°C.
To determine new reference points.
For ex. 4mA -> 0.00 m
and 20mA -> 8.50 m
Choose the
desired language
Select the desired
units
Select the desired
filter
Enter the
Sound velocity
Perform a Teach-In
procedure
Enter the current
output range
Configure relays
1 & 2 ( if available )
See section 4.4.1
See section 4.4.2
See section 4.4.3
See section 4.4.4
See section 4.4.6
See section 4.4.7
See section 4.4.8
Measurement or Simulation (optional)
See section 2.3