Burkert Type 8619 User Manual
Page 92
90
Adjustmentandcommissioning
Detailed procedure for teach-in by flow rate
→
Choose the flow rate unit in which teach-in is run:
Mx:Inputs
Calibration
DI1/2: Flow
M0:Inputs
Flow unit
Flow teaching
L/h
Igal/s
...
→
Run teach-in by flow rate:
→
Allow the fluid to circulate in the pipes and wait
for the flow rate to stabilise.
The multiCELL displays the K factor
calculated by teach-in.
OK
OK
OK
The multiCELL displays the flow rate
calculated with the current K factor
→
Enter the value of the flow rate
in the pipe.
0049 L/min
0001 L/s
Flow teaching
Calibration
DI1:/DI2:Flow
M0:Inputs
Start teaching
Meas. in progr.
Average flow
Flow K factor:
K=3,810
Teaching result
0005 L/min
The multiCELL calculates the flow rate
measured in the pipe, with the current K factor,
for 100 seconds
1)
.
The bargraph shows the time passed.
1)
Measurement can be suspended at any time by clicking on "OK".
Type 8619
english
- Type 1062 (112 pages)
- Type 8750 (82 pages)
- Type 1050 (4 pages)
- Type 8750 (64 pages)
- Type 8681 (40 pages)
- Type 8681 (90 pages)
- Type 8791 (4 pages)
- Type 8798 (106 pages)
- Type 8798 (2 pages)
- Type 8792 (252 pages)
- Type 8718 (34 pages)
- Type 8792 (118 pages)
- Type 8791 (15 pages)
- Type 8792 (136 pages)
- Type 8791 (106 pages)
- Type 8791 (184 pages)
- Type 8791 (28 pages)
- Type 8791 (21 pages)
- Type 8791 (154 pages)
- Type 0911 (76 pages)
- Type 0911 (46 pages)
- Type 0911 (64 pages)
- Type 0911 (84 pages)
- Type 1058 (31 pages)
- Type 1060 (4 pages)
- Type 1066 (112 pages)
- Type 1067 (158 pages)
- Type 1077-2 (33 pages)
- Type 1094 (12 pages)
- Type 1094 (41 pages)
- Type 1094 (82 pages)
- Type 1094 (126 pages)
- Type 1115 (25 pages)
- Type 1150 (99 pages)
- Type 1541 (2 pages)
- Type 5142 (6 pages)
- Type 8619 (40 pages)
- Type 8620 (177 pages)
- Type 8622 (4 pages)
- Type 8623 (130 pages)
- Type 8623 (90 pages)
- Type 8625 (118 pages)
- Type 8624 (124 pages)
- Type 8718 (254 pages)