26

Installationandwiring

7.3.4.

Wiring the output module "ouT"

The "OUT" outputs module has:

• Two 4-20 mA analogue outputs;

• Two digital outputs.

The outputs are galvanically insulated, and therefore voltage free.

+

-

+

-

1

I+

I-

I+

I-

FE

T+

T-

T+

T-

0 VDC

+

-

12-36 VDC

+

-

0 VDC

12-36 VDC

0 VDC

12-36 VDC

12-36 VDC

0 VDC

2 3 4 5 6 7 8 9

(AO1) (AO2)

(DO1) (DO2)

Load 2

Load 1

1st 4-20 mA

input (at external

instrument)

2nd 4-20 mA input (at
external instrument)

digital outputs

analogue outputs

(designation in the configuration menus of the Mx
additional output module)

FE = functional earth

Figure 12 :

Wiring the "OUT" output module

7.3.5.

Wiring the "ph/orp" module

• Wire a pH/redox sensor in symmetrical mode to obviate the influence of interference and, in this case,

wire the equipotential electrode (compulsory).

• When the pH/redox sensor is wired in asymmetrical mode, measurement of the pH or the oxidation

reduction potential may drift over time when the equipotential electrode is not wired.